8
Item
Unit
Outdoor Unit
Fan
Type
Propeller Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
—
Output Power
W
40
Fan Speed
rpm
Cooling: 950
Heating: 800
Heat Exchanger
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 28 × 17
Size (W × H × L)
mm
36.4 × 588 × 827.7 : 856.3
Power Source (Phase, Voltage, Cycle)
ø
Single
V
230
Hz
50
Input Power
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
kW
Cooling: 1.04
Heating: 0.64
Heating: 0.90
Maximum Input Power For Heatpump System
kW
2.35
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 11.0 / 2.35k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
1Ø / 13.0 / 3.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
— / — / —
Starting Current
A
3.0
Running Current
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
A
Cooling: 4.8
Heating: 3.0
Heating: 4.2
Maximum Current For Heatpump System
A
11.0
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
%
Cooling: 94
Heating: 93
Power Cord
Number of core
-
Length
m (ft)
-
Thermostat
Electronic Control
Protection Device
Electronic Control
Item
Unit
Indoor Unit
Performance Test Condition
EN 14511
Operation Range
Outdoor Ambient
°C
Cooling: 16 ~ 43
Heating: -20 ~ 35
Water Outlet
°C
Cooling: 5 ~ 20
Heating: 20 ~ 55
Internal Pressure Differential
kPa
Cooling: 5.0
Heating: 5.0
Noise Level
Condition
(Ambient/Water)
A35W7
dB (A)
Cooling: 28
Power Level dB
Cooling: 41
Dimension
Height
mm (inch)
892 (35-1/8)
Width
mm (inch)
500 (19-11/16)
Depth
mm (inch)
340 (13-13/32)
Net Weight
kg (lbs)
44 (97)
Refrigerant Pipe Diameter
Liquid
mm (inch)
6.35 (1/4)
Gas
mm (inch)
12.70 (1/2)
Water Pipe Diameter
Inlet
mm (inch)
28 (1-3/32)
Outlet
mm (inch)
28 (1-3/32)
Water Drain Hose Inner Diameter
mm (inch)
12 (15/32)
Pump
Motor Type
DC Motor
Input Power
W
30