101
16.5.9 Deice Circulation Error (H65)
Malfunction Decision Conditions:
During deice operation, flow switch detects water flow for 10 seconds during deice.
Malfunction Caused:
4. Secondary pump.
5. Flow switch faulty.
6. Water pump faulty.
7. Indoor PCB.
Abnormality Judgment:
Continue 10 seconds.
●
Relocate secondary pump to buffer tank
so that it does not circulate water to
indoor unit during deice
This error occurs during
deice operation
Is secondary
pump installed directly
to the indoor unit
Flow switch defective?
YES
●
Replace flow switch
YES
NO
Flow switch remain ON - check
flow switch direction and continuity
NO
Replace indoor PCB
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Caution
Troubleshooting: