93
14.1.6 Low
Frequency
Protection Control 2
When all the below conditions comply, the minimum compressor frequency will change to lower frequency.
Temperature, T, for:
Heating
Cooling
Outlet water (°C)
T < 14 or T
≥
48
T < 14 or T
≥
30
Outdoor air (°C)
T < 4 or T
≥
24
T < 13 or T
≥
38
Indoor heat exchanger (°C)
T
≥
0
T < 30
14.1.7 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection
period:
- After compressor on for 1 minute.
Detection
conditions:
- When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
- When abnormality is detected 4 times within 120 minutes, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
14.1.8 Outside Temperature Current Control
14.1.9 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control
content:
c. Trigger heater START condition
o
When the outdoor air temperature is below than 5°C, and discharge temperature is 11°C or below.
d. Resetting heater STOP condition
3.
When the outdoor air temperature exceeds entry condition (2°C)
4.
When the discharge temperature exceeds entry condition (5°C)
Compressor stop
Outdoor temperature
23°C
14°C
-25°C
21°C
-28°C
12°C
Max.
current
value is
regulated