80
12.9 Heater Control for Tank Side
Backup heater turn ON at tank side after fulfill below condition:
1 Tank Temperature < Tank Set Tempe [0°C]
AND
2 Heat Pump Thermo OFF.
AND
3 20 minutes from previous heater OFF.
AND
4 Remote controller Select USE for Backup Heater for Tank.
Backup Heater Turn OFF condition:
1 Tank Temperature > Tank Set Tempe [0°C] for continuously 15 seconds.
OR
2 Heat Pump Thermo ON.
OR
3 Mode Change or Operation OFF by remote controller.
* Backup Heater Turn ON/OFF all together according to the selected heater capacity.
12.10 Base Pan Heater Control (Optional)
To enable the base pan heater function, control panel initial setting has to be manually adjusted by activating
Base Pan Heater menu.
There are 2 optional start condition can be selected, Type A or Type B.
Control
details:
1 Type A: (Default Auto Mode)
Start conditions:
o
When outdoor air temperature
≤
3°C during heating and deice operation is ON.
Control contents:
o
Base pan heater is ON during deice operation and continues ON for 10 minutes after deice operation
ends.
Cancel condition:
o
When outdoor temperature > 6°C after deice end or
o
When operation is not at heating mode or
o
Base pan heater ON timer count is completed.
2 Type B: (ON Mode)
Start conditions:
o
When outdoor air temperature is
≤
5°C and operates in heating mode, base pan heater is ON.
Cancel conditions:
o
When outdoor air temperature is > 7°C or
o
When operation is not at heating mode.
Note:
* Base pan heater cannot be ON during test mode and standby mode.
Tank
Temp.
65°C
Tank Water Set Temp
Time
Heat Pump
Operation
Backup
Heater
Operation