73
3. Backup Heater Control:
o
During Cooling interval
Backup Heater will not operate during Cool Mode.
o
During tank heat-up interval
Backup Heater Turn ON condition:
Tank Temperature < Tank Set Tempe [0°C] AND
Heat Pump Thermo OFF AND
20 minutes from previous heater OFF. AND
Remote controller Select USE for Backup Heater for Tank.
Back up Heater Turn OFF condition:
Tank Temperature > Tank Set Tempe [0°C] for continuously 15 seconds
OR
Heat Pump Thermo ON
OR
Mode Change or Operation OFF by remote controller
* Turn ON all heater element according to the maximum heater selection when heater is request to ON
by remote controller.
4. 2-way vale control:
o
2-ways valve opens.
Cool + Tank mode
3 way valve
on
off
Heat Pump
on
off
Water Pump
on
off
Backup Heater
Tank Temp.
Water Temp.
on
off
51°C
51°C
65°C
48°C
58°C
58°C
65°C
65°C