69
o
Backup Heater Turn OFF condition:
1. Tank Temperature > Tank Set Tempe [0°C] for continuously 15 seconds.
OR
2. Heat Pump Thermo ON
OR
3. Mode Change or Operation OFF by remote controller.
* Turn ON All heater element according to the maximum heater selection when heater is request to ON by remote
controller.
d. 2 way valve control:
o
2 ways valve close.
Tank mode Tank set Temp. = 65°C
3 way valve
on
on
off
off
on
off
on
off
Heat Pump
Backup Heater
ID Water Pump
Tank Temp.
Water Outlet Temp.
Tank side
Tank Thermo OFF
51°C
65°C
58°C
48°C
57°C
57°C
57°C