15
2.4 WH-ADC0916G9E8 WH-UD09FE8
Item
Unit
Outdoor Unit
Performance Test Condition
EN 14511
Cooling Capacity
Condition
(Ambient/Water)
A35W7
kW 7.00
BTU/h 23900
kcal/h 6020
Cooling EER
W/W 3.17
kcal/hW 2.72
Heating Capacity
Condition
(Ambient/Water)
A7W35 A2W35
kW 9.00
9.00
BTU/h 30700
30700
kcal/h 7740
7740
Heating COP
W/W 4.84
3.59
kcal/hW 4.16
3.08
Noise Level
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
dB (A)
Cooling: 49
Heating: 49
—
Power Level dB
Cooling: 67
Heating: 66
—
Air Flow
m
3
/min (ft
3
/min)
Cooling: 89.5 (3160)
Heating: 76.8 (2710)
Refrigeration Control Device
Expansion Valve
Refrigeration Oil
cm
3
FV50S
(1200)
Refrigerant (R410A)
kg (oz)
2.55 (90.0)
Dimension
Height
mm (inch)
1340 (52-3/4)
Width
mm (inch)
900 (35-7/16)
Depth
mm (inch)
320 (12-19/32)
Net Weight
kg (lbs)
108 (238)
Pipe Diameter
Liquid
mm (inch)
9.52 (3/8)
Gas
mm (inch)
15.88 (5/8)
Standard Length
m (ft)
5 (16.4)
Pipe Length Range
m (ft)
3 (9.8) ~ 30 (98.4)
I/D & O/D Height Difference
m (ft)
20 (65.6)
Additional Gas Amount
g/m (oz/ft)
50 (0.5)
Refrigeration Charge Less
m (ft)
10 (32.8)
Compressor
Type
Hermetic
Motor
Motor Type
Brushless (4-poles)
Rated Output
kW
4.30
Fan
Type
Propeller
Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
—
Output Power
W
60
Fan Speed
rpm
Cooling: 550 (Top), 590 (Bottom)
Heating: 490 (Top), 530 (Bottom)
Heat Exchanger
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 51 x 18
Size (W × H × L)
mm
903.7 x 1295.4 x 38.1
Summary of Contents for WH-ADC0916G9E8
Page 34: ...34 4 2 Outdoor Unit Air inlet rear Air inlet side Air inlet side Air outlet Air outlet ...
Page 40: ...40 8 Wiring Connection Diagram 8 1 Indoor Unit RY HT L1 RY HT L2 RY V3 RY V2 RY HT L3 ...
Page 100: ...100 Note Default value refer Location of Control and Component OPERATION ACTUAL ...