149
18.6 To Remove Pressure Relief Valve, Flow Switch and Air Purge Valve
When reinstall Flow Switch, ensure the arrow on the flow switch is parallel with the pipe shaft and is facing in
the direction of flow.
During reinstall Air Purge Valve.
18.7 To Remove Water Pump
1. Remove 2 retaining rings.
4. Turn the flow switch anti-clockwise
then remove Flow Switch.
2. Pull down to remove
water hose.
3. Pull outward to remove
Pressure Relief Valve.
5. Turn the Air Purge Valve
anti-clockwise then remove.
Air Purge Valve
Pressure Relief Valve
Flow Switch
Packing
Apply some water based grease
on packing surface before fix
with shut off valve.
Make sure plug is fully close
in clockwise direction.
3. Remove 2 retaining rings, then pull
out the Water Pump.
2. Remove 2 screws from the water pump.
1. Disconnect CN-PUMP2 from
electronic controller.
Water Pump