12
2.3 WH-ADC0916G9E8 WH-UX16FE8
Item
Unit
Outdoor Unit
Performance Test Condition
EN 14511
Cooling Capacity
Condition
(Ambient/Water)
A35W7
kW 12.20
BTU/h 41600
kcal/h 10490
Cooling EER
W/W 2.56
kcal/hW 2.20
Heating Capacity
Condition
(Ambient/Water)
A7W35 A2W35
kW 16.00
16.00
BTU/h 54600
54600
kcal/h 13760
13760
Heating COP
W/W 4.28
3.10
kcal/hW 3.68
2.67
Noise Level
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
dB (A)
Cooling: 54
Heating: 53
—
Power Level dB
Cooling: 71
Heating: 70
—
Air Flow
m
3
/min (ft
3
/min)
Cooling: 109.4 (3860)
Heating: 76.0 (2680)
Refrigeration Control Device
Expansion Valve
Refrigeration Oil
cm
3
FV50S
(1200)
Refrigerant (R410A)
kg (oz)
2.90 (102.4)
Dimension
Height
mm (inch)
1340 (52-3/4)
Width
mm (inch)
900 (35-7/16)
Depth
mm (inch)
320 (12-19/32)
Net Weight
kg (lbs)
119 (262)
Pipe Diameter
Liquid
mm (inch)
9.52 (3/8)
Gas
mm (inch)
15.88 (5/8)
Standard Length
m (ft)
5 (16.4)
Pipe Length Range
m (ft)
3 (9.8) ~ 30 (98.4)
I/D & O/D Height Difference
m (ft)
20 (65.6)
Additional Gas Amount
g/m (oz/ft)
50 (0.5)
Refrigeration Charge Less
m (ft)
10 (32.8)
Compressor
Type
Hermetic
Motor
Motor Type
Brushless (4-poles)
Rated Output
kW
4.76
Fan
Type
Propeller
Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
—
Output Power
W
60
Fan Speed
rpm
Cooling: 680 (Top), 720 (Bottom)
Heating: 500 (Top), 540 (Bottom)
Heat Exchanger
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 51 x 19
Size (W × H × L)
mm
898.8 x 1295.4 x 44