111
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Correct arrangement of multiple mono-bloc devices with representation of the air flow
direction
Wrong
Correct
1 Minimum distance: 100 mm
1
5.2.3.3
Securing the mono-bloc unit
The mono-bloc unit must be mounted on a flat, horizontal and solid surface. Besides the weight of
the device, the weight of the water must also be taken into account. The unit is to be mounted with
four M12 anchor bolts, each having a tensile force of more than 15,000 N.
Minimum requirements for anchoring the mono-bloc unit on the ground by means of a
foundation (A and B) or directly in the floor plate (C)
All dimensions in mm
Note: Schematic figure for explanation purposes
only.
60
mm
300
mm
>
20
80
4
3
3
4
2
1
×
100
80
0
4
3
1
5
2
355
46
0
775
980
≥
30
0
200
≥
60
×
100
80
0
4
3
1
5
2
355
46
0
775
980
≥
30
0
200
≥
60
B
C
A
A Front view: Anchoring by means of foundation
1 Ground
2 Gravel filling
3 Strip foundation
4 Anchor bolts
5 Drain pipes
B Top view
C Detailed view: Anchoring in the floor plate
3 Strip foundation
4 Anchor bolts