Software Updates

Software updates can be downloaded from www.vossloh-schwabe.com. Customer-specific versions can be 

made available by your VS sales representative.

DHCP, Clients and Servers

DHCP Server: network device (virtual server) that allocates IP addresses.  

DHCP Client: network device that is given an IP address (by the DHCP Server).  

Server: the PC, industrial server or VS LightBox used to run Light Controller services.  

Client: operating device (e.g. tablet, notebook) within the same network that calls up the user interface.

Time and Date

If time-depedent controls are to be used (e.g. weekly schedules, night-lights), the system time of the LightBox 

must be set correctly. Synchronisation only needs a connection to the internet to be established. For the LightBox 

DHCP (186513), the function “Receive server time from this client” can alternatively be used in the “System -> 

Settings" menu. This is dependent on the correct time being set in the client (e.g. tablet).

Documentation of System Information

We recommend you download and keep a report at regular intervals to give you an overview of key data 

concerning your lighting system at all times. This report contains details of the system state, the configuration of 

the system components and the created luminaire groups.

Direct Access via Touch4Light

The report contains QR codes that take you directly to the Touch4Light user interface. An IP address does not 

need to be entered. However, it is necessary for the client (e.g. tablet) to be in the same WiFi network as the 

LightBox.

Labelling

We recommend you call up the names allocated during commissioning under “Configuration -> Labelling", print 

these out and attach them to the installed devices. This lets you, for instance, use a documented floor plan for 

quick identification of components.

Adding luminaires at a later point in time

Luminaires can also be integrated into the system at a later point in time using the Luminaire Search function.

CAUTION: Under certain circumstances, a DALI device that has already been addressed in another system can 

cause the luminaire address to be exchanged with an existing luminaire. This must be taken into consideration 

during group assignment.

Replacing luminaires

Components can be replaced specific to their position and function via the “Extended Functions”  

-> Replace Components menu.

Data Storage

System configuration settings can be saved under "System -> Settings -> Download Current Settings". We 

recommend this download step is performed after every relevant change of the configuration settings. This file 

should not be saved on the server, but at another storage location as a backup file.

Restore System

Saved system configuration settings can be restored (e.g. in the event of server failure or incorrect configura-

tion). Given an unchanged DALI installation, simply load the file under: "System -> Settings -> Load system 

settings".

Mail Reporting

To receive email updates on events or system status, you will need a mail server, for which purpose http://

www.hmailserver.com can be used, among others.

Firewall

The firewall is already preconfigured for the LightBox. Should you prefer to use your own server, at least the 

following ports must be approved for sharing: 80 (TCP incoming), 31459 (UDP outgoing), 31460 (UDP 

incoming), 31460 (TCP incoming), 31461 (TCP incoming)

Connection Problems affecting the  

Light Controller

Should the system develop problems, e.g. if the DALI bus is not recognised, a restart of the Light Controller can 

be forced by briefly disconnecting and reconnecting it from the mains. Attention: This procedure may only be 

carried out by authorised and fully qualified staff.

Disconnecting Coupled Devices

If a Light Controller is not recognised by the server or if a different server needs to be used, coupled devices 

will first need to be disconnected by pressing the “Disconnect” button on the Light Controller for approx. 10 

seconds. The Light Controller can then be reintegrated into the system of your choice via the “Light Controller” 

commissioning menu.

Reset System

The system can be reset under "System -> Settings -> Reset to default settings". This process deletes all configura-

tion settings. However, please note that performing this step will also render all data backups unusable. It is 

therefore recommended to carry out this step only if the system is to be fundamentally repurposed.

Contact:

 

please contact your VS representative or send an email to: [email protected]

5

Quick Start Guide Light Controller IP/DALI

Quick-Star

t-Guide_Light Controller IP_EN_08. Juli, 2019

Vossloh-Schwabe Deutschland GmbH

 · Hohe Steinert 8 · 58509 Lüdenscheid · Germany · Tel. +49 (0) 23 51/10 10 · Fax +49 (0) 23 51/10 12 17 · www.vossloh-schwabe.com

A Member of the Panasonic Group

Summary of Contents for Vossloh-Schwabe Light Controller IP/DALI 2CH

Page 1: ... N Only one DHCP server may be installed in the network at any time Operating Option 1 Server based Installation LightBox DHCP Connect a monitor via HDMI We recommend setting the pre installed Mozilla Firefox browser as your default browser Open browser and enter the following URL http 127 0 0 1 Operating Option 2 Client based Installation e g tablet or PC For LightBox DHCP Ref No 186513 Wireless ...

Page 2: ...ires Line B Group 1 Group 2 Menu Luminaire Search Setup Menu Functional Mapping Buttons Touch 4 Light DALI Scene Sensors Advanced Functions e g timer program Menu Grouping Quick Start Guide Light Controller IP DALI Quick Start Guide_Light Controller IP_EN_08 Juli 2019 Vossloh Schwabe Deutschland GmbH Hohe Steinert 8 58509 Lüdenscheid Germany Tel 49 0 23 51 10 10 Fax 49 0 23 51 10 12 17 www vossloh...

Page 3: ...ting call up lighting scenes and activate time controlled light sequences IMPORTANT Integrating VS Extenders will limit the entire system to its basic control and adjustment functions Please observe the information provided on page 5 3 CONFIGURATION OF SYSTEM COMPONENTS Creation of Luminaire Groups Configuration Groups Allocate group name e g office kitchen hallway etc Assign luminaires to the gro...

Page 4: ...ed into the Group Functions menu Daily Schedule Weekly Schedule Astronomical control Room plan Component replacement Flexible room usage EnOcean Night guard Group dynamics Random RGB behavior IMPORTANT N This is dependent on the correct system time being set in the LightBox NOTES ON USING VS EXTENDERS VS Extenders provide an affordable option for simultaneously addressing bundling up to 64 DALI co...

Page 5: ...c to their position and function via the Extended Functions Replace Components menu Data Storage System configuration settings can be saved under System Settings Download Current Settings We recommend this download step is performed after every relevant change of the configuration settings This file should not be saved on the server but at another storage location as a backup file Restore System S...

Page 6: ...40 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 Secure Area Inadmissible Area Quick Start Guide Light Controller IP DALI Quick Start Guide_Light Controller IP_EN_08 Juli 2019 Vossloh Schwabe Deutschland GmbH Hohe Steinert 8 58509 Lüdenscheid Germany Tel 49 0 23 51 10 10 Fax 49 0 23 51 10 12 17 www vossloh schwabe com A Member of the Panasonic Group 6 ...

Reviews: