background image

Software-based Commissioning

 

Â

Open browser

 

Â

Enter IP address (see Network-based Commissioning)

 

Â

Enter user name/password

 

Â

Accept the licence agreement 

IMPORTANT

N

The Light Controller IP/DALI is delivered with the 
following user name and password: "admin". This 
should be changed following commissioning.

Starting the Setup Procedure for the  
Light Controller IP/DALI

 

„

1. LANGUAGE SELECTION

System -> Settings -> select desired language.

 

„

2. SETUP

Recognition and integration of system components

• Select the Light Controllers and then integrate them into the 

system via "Search", followed by confirmation with "Connect".

•  Integrate luminaires (DALI control gear) and DALI input (input 

devices: DALI push button and sensors) into the system by indi-
vidual lines and allocating names.

• Mains buttons are integrated into the system by allocating 

names to the connected wired buttons.

• EnOcean components (wireless push buttons, door/window 

contacts) must be pressed to be identified by the Light Control-
ler. System integration follows name allocation.

• Touch4Light  

This lets you create your own switches and switch functions for 
lighting control purposes as well as to activate or deactivate 
certain components. The provided push-button and sliding con-
trols also let you use – a tablet PC or a smartphone to – switch 
light on or off, dim lighting, call up lighting scenes and activate 
time-controlled light sequences.

• IMPORTANT: Integrating VS Extenders will limit the entire system 

to its basic control and adjustment functions. Please observe the 
information provided on page 5.

 

„

3. CONFIGURATION OF SYSTEM COMPONENTS

Creation of Luminaire Groups

Configuration -> Groups

• Allocate group name (e.g. office, kitchen, hallway, etc.)
• Assign luminaires to the groups

IMPORTANT

N

It is not possible to integrate luminaires into more than 
one group. For that reason, it is recommended to 
create logical, functional groups. Functions that apply 
to multiple groups can be set in the "Group Functions" 
menu.  

 

– Option 1: Assign all luminaires to one group. All luminaires 

of all DALI lines can be assigned to a single group.

 

– Option 2: Individually assign luminaires to a specific group.

 

– Time-saving assignment: in addition, it is possible to use a 

webcam (e.g. tablet PC) to identify a luminaire and thus as-
sign it to a group.

 
Definition of Group Functions

Configuration -> Group Functions 

• Select the group whose functions you wish to configure. Groups 

are listed alphabetically.

• Default setting of the minimum dimming level: 126 = 3% 

(recommended for commonly available DALI control gear). This 
value can be changed using the slider.

3

Quick Start Guide Light Controller IP/DALI

Quick-Star

t-Guide_Light Controller IP_EN_08. Juli, 2019

Vossloh-Schwabe Deutschland GmbH

 · Hohe Steinert 8 · 58509 Lüdenscheid · Germany · Tel. +49 (0) 23 51/10 10 · Fax +49 (0) 23 51/10 12 17 · www.vossloh-schwabe.com

A Member of the Panasonic Group

Summary of Contents for Vossloh-Schwabe Light Controller IP/DALI 2CH

Page 1: ... N Only one DHCP server may be installed in the network at any time Operating Option 1 Server based Installation LightBox DHCP Connect a monitor via HDMI We recommend setting the pre installed Mozilla Firefox browser as your default browser Open browser and enter the following URL http 127 0 0 1 Operating Option 2 Client based Installation e g tablet or PC For LightBox DHCP Ref No 186513 Wireless ...

Page 2: ...ires Line B Group 1 Group 2 Menu Luminaire Search Setup Menu Functional Mapping Buttons Touch 4 Light DALI Scene Sensors Advanced Functions e g timer program Menu Grouping Quick Start Guide Light Controller IP DALI Quick Start Guide_Light Controller IP_EN_08 Juli 2019 Vossloh Schwabe Deutschland GmbH Hohe Steinert 8 58509 Lüdenscheid Germany Tel 49 0 23 51 10 10 Fax 49 0 23 51 10 12 17 www vossloh...

Page 3: ...ting call up lighting scenes and activate time controlled light sequences IMPORTANT Integrating VS Extenders will limit the entire system to its basic control and adjustment functions Please observe the information provided on page 5 3 CONFIGURATION OF SYSTEM COMPONENTS Creation of Luminaire Groups Configuration Groups Allocate group name e g office kitchen hallway etc Assign luminaires to the gro...

Page 4: ...ed into the Group Functions menu Daily Schedule Weekly Schedule Astronomical control Room plan Component replacement Flexible room usage EnOcean Night guard Group dynamics Random RGB behavior IMPORTANT N This is dependent on the correct system time being set in the LightBox NOTES ON USING VS EXTENDERS VS Extenders provide an affordable option for simultaneously addressing bundling up to 64 DALI co...

Page 5: ...c to their position and function via the Extended Functions Replace Components menu Data Storage System configuration settings can be saved under System Settings Download Current Settings We recommend this download step is performed after every relevant change of the configuration settings This file should not be saved on the server but at another storage location as a backup file Restore System S...

Page 6: ...40 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 Secure Area Inadmissible Area Quick Start Guide Light Controller IP DALI Quick Start Guide_Light Controller IP_EN_08 Juli 2019 Vossloh Schwabe Deutschland GmbH Hohe Steinert 8 58509 Lüdenscheid Germany Tel 49 0 23 51 10 10 Fax 49 0 23 51 10 12 17 www vossloh schwabe com A Member of the Panasonic Group 6 ...

Reviews: