6-3
6-2
6. Test run
6. TEST RUN
6-1. Preparing for Test Run
Before attempting to start the air conditioner,
check the following:
(1) All loose matter is removed from the cabinet espe-
cially steel filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
(3) The protective spacers for the compressor used for
transportation have been removed. If not, remove
them now.
(4) The transportation pads for the indoor fan have been
removed. If not, remove them now.
(5) The power has been supplied to the unit for at least
5 hours before starting the compressor. The bottom
of the compressor should be warm to the touch and
the crankcase heater around the feet of the com-
pressor should be hot to the touch. (Fig. 6-1)
(6) Both the gas and liquid tube service valves are open.
If not, open them now. (Fig. 6-2)
(7) Request that the customer be present for the trial
run.
Explain the contents of the instruction manual, then
have the customer actually operate the system.
(8) Be sure to give the instruction manual and warranty
certificate to the customer.
(9) When replacing the control PCB, be sure to make all
the same settings on the new PCB as were in use
before replacement.
The existing EEPROM is not changed, and is
connected to the new control PCB.
Fig. 6-1
Fig. 6-2
Power mains switch
(Power must be turned ON
at least 5 hours before
attempting test run)
ON
Liquid tube
Gas tube
6
SM830203-04.indb 2
15/10/14 16:25:08
Summary of Contents for U-26PE1U6
Page 8: ...vii MEMO...
Page 77: ...1 69 1 Specifications 1 4 Dimensional Data Outdoor Unit U 42PE1U6 U 42PS1U6 1...
Page 218: ...2 12 MEMO...
Page 219: ...3 1 3 2 Indoor Units 3 2 Outdoor Units 3 14 3 ELECTRICAL DATA 3 1 3...
Page 220: ...3 2 3 Electrical data 3 1 Indoor Units Concealed Duct Type S 26PF2U6 S 36PF2U6 3...
Page 221: ...3 3 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Page 222: ...3 4 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Page 223: ...3 5 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Page 224: ...3 6 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Page 225: ...3 7 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Page 226: ...3 8 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Page 227: ...3 9 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Page 228: ...3 10 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Page 230: ...3 12 3 Electrical data Wall Mounted Type S 26PK2U6 3...
Page 232: ...3 14 3 Electrical data 3 2 Outdoor Units U 26PE1U6 3...
Page 233: ...3 15 3 Electrical data U 26PE1U6 3...
Page 234: ...3 16 3 Electrical data U 26PS1U6 3...
Page 235: ...3 17 3 Electrical data U 26PS1U6 3...
Page 236: ...3 18 3 Electrical data U 36PE1U6 3...
Page 237: ...3 19 3 Electrical data U 36PE1U6 3...
Page 238: ...3 20 3 Electrical data U 36PS1U6 3...
Page 239: ...3 21 3 Electrical data U 36PS1U6 3...
Page 240: ...3 22 3 Electrical data U 42PE1U6 3...
Page 241: ...3 23 3 Electrical data U 42PE1U6 3...
Page 242: ...3 24 3 Electrical data U 42PS1U6 3...
Page 243: ...3 25 3 Electrical data U 42PS1U6 3...
Page 244: ...MEMO 3 26...
Page 284: ...5 24 MEMO...
Page 297: ...201510...