background image

SPECIFICATIONS

3

Total 0.4A or less (including the current consump-

tion of this unit and the connected devices)

Allowable through 

current

PNP open-collector transistor

(Photo-coupler isolation)

Maximum source current: 100mA

Applied voltage: 30V DC or less

(between output and +V)

Residual voltage: 

1.5V or less 

(at 100mA source current)

0.4V or less

(at 16mA source current)

Output

(Output 1, Output 2)

NPN open-collector transistor

(Photo-coupler isolation)

Maximum sink current: 100mA

Applied voltage: 30V DC or less

(between output and 0V)

Residual voltage: 

1.5V or less 

(at 100mA sink current)

0.4V or less 

(at 16mA sink current)

PNP type

Model No.

S-LINK

 side: 0.5mm

2

 4-core flat cable 0.6m long

Users' device side: 0.5mm

2

 4-core flat cable 0.4m long

Cable

55g approx.

Weight

Material

Polycarbonate

35 to 85% RH, Storage: 35 to 85% RH

Ambient humidity

0 to +55

 (No dew condensation), Storage: -20 to +70

Ambient temperature

Green LED (blinks to indicate the synchronizing 

signal sent from the 

S-LINK

 control unit)

Transmission

indicator

Output 1 indication: Orange LED

(lights up when the output 1 is ON)

Output 2 indication: Green LED

(lights up when the output 2 is ON)

Two output

Output point

Operation indicator

The output transistor turns on when the 

S-LINK

 sends the 

output signal assigned ON through the transmission line.

Output operation

2.4

FAN-in

Current consumption

24V DC

±

10% (supplied from the 

S-LINK

 control

unit or other power supplies)

Supply voltage

6mA or less

(except for connected devices)

12mA or less

(except for connected devices)

Item

SL-CH22

SL-CH22-PN

NPN type

Type

Please refer to the '

S-LINK Design Manual

' for details 

of the entire 

S-LINK

 system.

2 channel output unit

SL-CH22

 or 

SL-CH22-PN

Users' output device

(Electromagnetic valve etc.)

ADDRESSON

1 2 4 8

16

32 64

OFF

SL-CH22

SEND

OUT1

OG

I

O

SIDE

NOT

USED

OUT2

GN

OUTLINE

1

This links two output devices to the 

S-LINK

 system.

<Application>

The

S-LINK

 system control the double solenoid valves 

through the 

SL-CH22

 or the 

SL-CH22-PN

.

ADDRESS SETTING

6

Make sure to operate the switch while the power is off 

and after taking countermeasures, such as, wrist 

strap, etc., against electrostatic charge.

The address of output 1 is 127 or less. If the address 

of output 2 is over 127, the 

S-LINK

 system does not 

work properly.

The address of output 1 is given by the sum of all val-

ues that corresponding bits are set ON, and the ad-

dress of output 2 is made up by adding one to output 1 

address.

The address range is;

Output 1: 0 to 126, Output 2: 1 to 127

The right-most bit is not assigned (NOT USED).

No matter which it is ON or OFF.

(e.g.)

Output 1 address = 2 + 4 + 32 = 38

Output 2 address = (Output 1 address) + 1

= 38 + 1 = 39

Address set-up switch

ON

1

2

4

8

16

32

64

OFF

NOT

USED

The

MS-SLH

 (optional) can fix the 

SL-CH22

 and 

the

SL-CH22-PN

.

Mount the 

MS-SLH

 with M4 pan head screws.

The tightening torque should be 0.8N

m or less.

Press the 

SL-CH22

 or the 

SL-CH22-PN

 onto the 

MS-SLH

.

Note:

M4 pan head screws are not enclosed with 

MS-SLH

. Please 

arrange them separately.

2 CHANNEL OUTPUT UNIT 

HOLDER MS-SLH (OPTION)

7

<Mounting>

Insert a flathead driver into the gap between them 

as below.

Tilt the flathead screwdriver outward.

<Dismounting>

ADDRESSON

1 2 4 8

16 32 64

OFF

SEND

OUT1

OG

I

O

SIDE

OUT2

GN

NOT

USED

SL-CH22

ADDRESSON

1 2 4 8

16 32 64

OFF

SL-CH22

I

O

SIDE

OUT1

OG

OUT2

GN

NOT

USED

SEND

Thank you very much for using Panasonic products. 

Please read this Instruction Manual carefully and 

thoroughly for the correct and optimum use of this 

product. Kindly keep this manual in a convenient place 

for quick reference.

Never use this product with a device for 

personnel protection.

In case of using devices for personnel 

protection, use products which meet laws 

and standards, such as OSHA, ANSI or 

IEC etc., for personnel protection appli-

cable in each region or country.

Before touching this product, remove any 

electrostatic charge that may be present 

on your body. There is a danger of this 

product getting damaged due to the elec-

trostatic charge.

WARNING

PART DESCRIPTION

2

ADDRESS

ON

1

2

4

8

16

32

64

OFF

SL-CH22

SEND

OUT1

OG

I

O

SIDE

NOT

USED

OUT2

GN

G (Black)

D (White)

0V (Blue)

+24V (Brown)

OUT 2 (Pink / Gray)

OUT 1 (Pink)

0V (Blue)

+24V (Brown)

Address set-up switch

Use a long-tapered tool 

of which tip is less than 

0.8mm wide to toggle 

the switches, tweezers 

or the like.

Make sure to operate the 

switch while the power is 

off and after taking coun-

termeasures, such as, 

wrist strap, etc., against 

electrostatic change.

Brinks in corresponding 

to the synchronizing sig-

nal sent from the 

S-LINK

control unit

Transmission indicator

(Green)

Output 1 indication: Orange

(Lights up when the output 1 is ON)

Output 2 indication: Green

(Lights up when the output 2 is ON)

Operation indicator

(2-color indicator)

S-LINK

 side (LINK SIDE) 

flat cable of 0.6m long with 

0.5mm

2

 conductor tin-plated

Users' device side (I/O 

SIDE) flat cable of 0.4m 

long with 0.5mm

2

 conduc-

tor tin-plated

OUTPUT CIRCUIT DIAGRAMS

4

NPN type / SL-CH22

The output does not incorporate a short-circuit protection 

circuit. Do not connect it directly to a power supply or a 

capacitive load.

PNP type / SL-CH22-PN

Symbols... Z

D1

, Z

D2

, Z

D3

, Z

D4

: Surge absorption zener diode

T

r1

, T

r2

: NPN output transistor

T

r3

, T

r4

: PNP output transistor

+24

 DC (Brown)

(Brown) +24

 DC

(Pink / Gray) Output 2

(Pink) Output 1

(Blue) 0V

100mA max.

100mA max.

 D (White)

 G (Black)

 0V (Blue)

Color code

Color code

Z

D1

T

r1

S-LINK

 side

(LINE SIDE)

Internal circuit

Uses' device side

(I/O SIDE)

Z

D2

T

r2

Load

Load

Main circuit

+24

 DC (Brown)

(Brown) +24

 DC

(Pink / Gray)

Output 2

(Pink) Output 1

(Blue) 0V

100mA max.

100mA max.

 D (White)

 G (Black)

 0V (Blue)

Color code

Color code

Z

D4

T

r4

Z

D3

T

r3

Load

Load

S-LINK

 side

(LINE SIDE)

Internal circuit

Uses' device side

(I/O SIDE)

Main circuit

CONNECTING CABLE

5

Make sure that the power supply is off while wiring.


Connecting Users' output devices

Using the socket-branch hook-up connector 

SL-JK

(for cable end) or 

SL-JK1

 (for T-branching) and the 

snap male connector 

SL-CP1

 (for 0.08 to 0.2mm

2

 ca-

ble) or 

SL-CP2

 (for 0.3mm

2

 cable) enables to save

the connection work for output devices. However, take 

care that there are output devices which can not be 

connected.

Refer to the instruction manual enclosed with each 

connector for details.


Connecting S-LINK line

Use the 

SL

 connector to 

hook up 

S-LINK

 side cable 

of the 

SL-CH22

 or the

SL-CH22-PN

to the 

S-LINK

field cable.

Colors should be matched 

between both cable.

ADDRESSON

1 2 4 8 16 32 64

OF

F

SL-CH22

SEND

OUT1

OG

I

O

SIDE

OUT2

GN

NOTUSED

SL

 connector

S-LINK

field

Color matching

ADDRESSON

1 2 4 8 16 32 64

OFF

SL-CH22

SEND

OUT1

OG

I

O

SIDE

OUT2

GN

NOT

USED

Users' output device

(Beacon etc.)

Users' output

device

(Relay etc.)

SL-JK1

 (Blue)

(For T-branching)

SL-CP1

 or

SL-CP2

SL-JK

 (Light blue)

(For terminating)

SL-CP1

 or

SL-CP2

INTENDED PRODUCTS FOR

CE MARKING

9

The models listed under '

SPECIFI-

CATIONS

' come with CE Marking.

As for all other models, please contact our 

office.

3

CAUTIONS

8

This product has been developed / produced for in-

dustrial use only.

SL-CH22, SL-CH22-PN

Sensor & Wire-saving Link System 

S-LINK

2 Channel Output Unit

INSTRUCTION

MANUAL

MJEC-SLCH22 No.0055-62V

Contact  for CE

Panasonic Marketing Europe GmbH Panasonic Testing Center

Winsbergring 15, 22525 Hamburg,Germany

http://panasonic.net/id/pidsx/global

© Panasonic Industrial Devices SUNX Co., Ltd. 2016

PRINTED IN JAPAN

Overseas Sales Division (Head Office) 

2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan 

Phone: +81-568-33-7861  FAX: +81-568-33-8591

For sales network, please visit our website.