96
Input Select
■ 1NC
Used to connect the safety device of 1NC contact output. In this case, the category of the sys-
tem including this device is specified to be category 2 or less.
■ PNP×2 (dif.)
Used to connect safety devices (PNP semiconductor output × 2). The safety device to be used
is a type that turns “ON-OFF” two outputs alternately.
■ PNP×1
Used to connect a safety device (PNP semiconductor output × 1). In this case, the category of
the system including this device is specified to be category 2 or less.
■ No logic
If the number of safety devices in connection is less than 4, they are used for unused input
block. If a safety device is connected, the operation is not reflected.
<Reference>
For the connectable input blocks, and combinations of them with control blocks, refer to “
”.
5-11-2 Setting of Contact Input Mismatch Allowable Time
Setting “2NC” or “1NO / 1NC” in the input block displays a small blue window.
Mismatch allowable time is set between two inputs by using up-down arrows in
the input block or by direct entry.
Settable range
Initial setting
Input mismatch allowable time 0 (unlimited) to
60 sec. (in units of 0.01 sec.)
1 sec.