Before Using This Product
WUME-SCHG1C-4
1-7
1-5 Description of parts
1
2
3
4
5
7 6
8
10
9
11
<Switch cover removed>
Name
Function
1
Station number setting
switch
Set the CC-Link station number to a value from 1 to 64.
(Do not set to 0, or 65 or higher.)
[Factory default state: 1]
2
Communication speed
setting switch
Set the CC-Link communication speed.
0: 156 kbps, 1: 625 kbps, 2: 2.5 Mbps, 3: 5 Mbps, 4: 10 Mbps
[Factory default state: 156 kbps]
3
CC-Link connector
Connect to the master station or another slave station.
4
Male connector
Connect to a master controller or slave controller.
5
ERR. indicator (Red)
Lights up when CC-Link communication is interrupted. Blinks when a communi-
cation error occurs.
6
Power indicator (Green) Lights up when power is supplied.
7
RD indicator (Green)
Lights up during data reception.
8
L RUN indicator (Green) Lights up during data link execution.
9
SD indicator (Green)
Lights up during data sending.
10
L ERR. indicator (Red)
Lights up if the station number setting switch and communication speed setting
switch are in an invalid setting position when the power is turned on.
Blinks if the switch type setting is changed while the power is on.
11
Mode setting switch
Set the communication method and number of occupied stations.
[Factory default state: CC-Link mode 1]
• CC-Link mode 1
SW No.
1
2
3
4
5
6
7
8
ON / OFF ON OFF
Not used (Note)
Remarks CC-Link Ver. 1.10, number of occupied stations: 4
• CC-Link mode 2
SW No.
1
2
3
4
5
6
7
8
ON / OFF OFF ON
Not used (Note)
Remarks
CC-Link Ver.2.00, Number of occupied stations: 2
stations
Expanded cyclic transmission speed: x8
• CC-Link mode 3
SW No.
1
2
3
4
5
6
7
8
ON / OFF ON
ON
Not used (Note)
Remarks
CC-Link Ver.2.00, Number of occupied stations: 4
stations
Expanded cyclic transmission speed: x4
Note: Always keep unused switches in the OFF position.
Summary of Contents for SC-HG1-C
Page 2: ...WUME SCHG1C 4 2 MEMO ...
Page 8: ...WUME SCHG1C 4 8 MEMO ...
Page 16: ...WUME SCHG1C 4 1 8 MEMO ...
Page 17: ...2 1 2 System Configuration 2 1 Communication unit system 2 2 2 2 Unit types 2 4 ...
Page 22: ...WUME SCHG1C 4 2 6 MEMO ...
Page 106: ...WUME SCHG1C 4 4 72 MEMO ...
Page 107: ...5 1 5 Specifications 5 1 Specifications 5 2 5 2 Dimensions 5 3 ...
Page 110: ...WUME SCHG1C 4 5 4 MEMO ...
Page 111: ...6 1 6 Warranty 6 1 When you purchase and use the product 6 2 ...
Page 114: ...WUME SCHG1C 4 6 4 MEMO ...
Page 124: ...WUME SCHG1C 4 8 8 MEMO ...
Page 126: ... MEMO ...
Page 127: ... MEMO ...