Page 2: ...is generated in the used power supply connect a surge absorber to the supply and absorb the surge WIRING z Do not run the wires together with high voltage lines or power lines or put them in the same raceway This can cause malfunction due to induction z Make sure that the power is off while wiring z In order to reduce noise make the wiring as short as possible z Always use the specified transmissi...

Page 3: ...DESCRIPTION ձ S LINK system terminal block Connect the signal cable and power supply of the S LINK system The S LINK system terminal block is connector type and it is possible to wire it after removing it from SL PCAT ...

Page 4: ...Set the first 3 digits of the 4 digits PC AT hexadecimal I O address The lowest digit is fixed 0H to FH Ensure that the address does not overlap with the I O address used on other boards Notes 1 Set the I O address in binary number 2 In PC AT set M 2 M 1 1 ON 3 L 1 is always 0 regardless of the setup Example In case I O first address 0300H No Binary ON OFF 1 4 0 㸫 2 3 0 OFF 4 2 0 OFF L 8 1 0 0 OFF...

Page 5: ...ng abnormal condition off ն Error indicator Red It lights up when an error occurs on the S LINK system main branch cable Notes 1 When ERROR 1 alone occurs the short circuit protection between D G is operative Release the short circuit protection function by rectifying the cause of the fault after switching off external power supply The short circuit protection function is maintained during the per...

Page 6: ...0H HML㸩1 4 Bank change over request register write into SL PCAT HML㸩1 5 Bank change over response register read out from SL PCAT HML㸩1 6 System set HML㸩1 7 Frame check HML㸩1 8 Number of S LINK units where ERROR 4 occurs HML㸩1 9 Number of connected S LINK I O units HML㸩1 A I O points HML㸩1 B Address of SL BS1A where operation stops HML㸩1 C Address of connected SL BS1A HML㸩1 D Unused 00H HML㸩1 E HML...

Page 7: ...you overwrite with the next output data 2 In case output data is mistakenly written into an input unit the written data is ignored and new input data is set after 1 4 to 10 7 ms In case Bank change over response register 01H It shows the addresses of S LINK I O units at which ERROR 4 has occurred When a bit is 1 ERROR 4 cable disconnection or abnormal S LINK I O unit has occurred at the S LINK I O...

Page 8: ...he output data to the S LINK output unit So transmission error of output data will be prevented if you write in the next output data after its returning to 0 is confirmed by the program Notes 1 ERROR 1 3 are held on until the cause of the error is removed 2 ERROR 4 can be released 0 by supplying power either to the S LINK system side or to the personal computer PC AT once again Although release ca...

Page 9: ... to 03H into ն HML 1 5 Bank change over response register Notes 1 In case a number other than 00H to 03H is written into յ HML 1 4 Bank change over request register it compulsorily changes over bank to 00H The output data is stored till the new output data is next written 2 Do not read out ձ HML 0 to HML F until ն HML 1 5 Bank change over response registe has been changed over շ HML 1 6 System set...

Page 10: ... LINK I O units It indicates the number of connected S LINK I O units ջ HML 1 A Number of I O points It indicates the number of I O points set by Mode switch SA 0 and SA 1 One of the numerical values 32 64 96 or 128 is indicated ռ HML 1 B Address of SL BS1A where operation stops ս HML 1 C Address of connected SL BS1A Booster SL BS1A s connection and operation conditions are indicated HML 1 B Conne...

Page 11: ...PCAT SAMPLE PROGRAM H9 3 1 PT H300 I O Address 0300H to 031FH OUT PT H12 H1 0 to 15 Output 16 to 127 Input OUT PT H14 0 Bank change over request register 0 WHILE INP PT H15 0 Wait for bank change over response register 0 WEND OUT PT 0 HFF 0 to 7 Output ON OUT PT 1 HFF 8 to 15 Output ON FOR I 0 TO 15 Read out and display ON OFF condition of 0 to 127 DT INP PT I PRINT INPUT OUTPUT DATA I RIGHT 0 HEX...

Page 12: ...e connected S LINK I O devices D and G lines only and the current consumption of the S LINK control board 3 The current consumption of the load is the sum of the current consumed by the devices sensors switches actuators etc connected to the S LINK I O devices Since fuse for replacement is not provided please arrange it separately ȭ5 2mm 20mm 5A ...

Page 13: ... length between the main power supply and the controller should be less than 10m 2 When the power is supplied from S LINK controller to I O devices at a cable distance of more than 10m add a surge absorber between 24V and 0V at a cable distance of less than 10m Recommended surge absorber ERZ05D390 Manufactured by Matsushita Electronic Components Co Ltd 3 Use a local power supply at a cable distanc...

Page 14: ... 13 8 DIMENSIONS Unit mm ...

Page 15: ... environment such as Delphi Visual Basic etc which does not have I O access commands z If you desire to use the library driver you may download it free of charge from our website http panasonic electric works net sunx z In case you cannot use our internet home page please contact our sales office Applicable OS Windows95 WindowsNT Ver 3 51 4 0 Applicable hardware IBM PC AT compatibles NEC PC FC 98 ...

Page 16: ...L SPECIAL OR CONSEQUENTIAL DAMAGES OF ANY KIND GENERAL TERMS AND CONDITIONS 4 OR ANY DAMAGES RESULTING FROM LOSS OF USE BUSINESS INTERRUPTION LOSS OF INFORMATION LOSS OR INACCURACY OF DATA LOSS OF PROFITS LOSS OF SAVINGS THE COST OF PROCUREMENT OF SUBSTITUTED GOODS SERVICES OR TECHNOLOGIES OR FOR ANY MATTER ARISING OUT OF OR IN CONNECTION WITH THE USE OR INABILITY TO USE THE PRODUCTS 4 CAUTIONS FO...