40
How to connect wiring to the terminal
■
For stranded wiring
(1) Cut the wire end with cutting pliers, then
strip the insulation to expose the stranded
wiring about 10 mm and tightly twist the
wire ends.
(2) Using a Phillips head screwdriver, remove
the terminal screw(s) on the terminal board.
(3) Using a ring connector fastener or pliers,
securely clamp each stripped wire end with
a ring pressure terminal.
(4) Place the ring pressure terminal, and
replace and tighten the removed terminal
screw using a screwdriver.
■
Examples of shield wires
(1) Remove cable coat not to scratch braided
shield.
(2) Unbraid the braided shield carefully and
twist the unbraided shield wires tightly
together. Insulate the shield wires by
covering them with an insulation tube or
wrapping insulating tape around them.
(3) Remove coat of signal wire.
(4) Attach ring pressure terminals to the signal
wires and the shield wires insulated in Step
(2).
Stranded wire
Ring
pressure
terminal
Strip 10 mm
Insulating tape Shield mesh
8 mm
Insulating tape
Shield mesh
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire
hazard may also occur. Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the instructions on “How to connect
wiring to the terminal” and fasten the wire securely with the terminal screw.
Screw and
Special washer
Ring
pressure
terminal
Terminal board
Ring pressure
terminal
Screw
Special
washer
Wire
Wire
01_330200_EU_Eng.indb 40
2021/1/13 10:23:11