61
DHW PAW-VP - Installation manual – 2020-05
How to make Settings
8
8.1.4 Detailed settings for indoor/outdoor unit CZ-RTC5B/RTC4/2
The new value must be set during the commissioning.
8.1.5 Setting Flow Chart
The system is in a fault-free state so that a safe commissioning can take place. All valid rules
have been followed.
!
Important
To follow exactly the described steps at the following flow chart is mandatory.
No.
Action
Note
1
Check if all temperature sensors are correctly
connected. All jumpers/bridged plugs (if any)
according to the wiring diagram, power supply and
communication wires are connected as shown in the
electrical wiring diagram.
2
3
Wait until initialization is finished.
4
Described at pages before:
Setting Procedure for Remote Controller Model
CZ-RTC5B
5
Attention:
After the setting "DN" 10 & 11 go out of detailed
setting:
Follow described at pages before:
Setting Procedure for Remote Controller Mode
CZ-RTC5B
See corresponding "DN" code list described on the
following pages, (combination for combination) for
Indoor Unit.
6
7
Described at pages before:
Setting Procedure for Remote Controller Model
CZ-RTC5B
8
Wait until initialization is finished.
9
Described at pages before: Detailed Setting Procedure
for Remote Controller Model CZ-RTC2 / CZ-RTC4
10
See corresponding "DN" code list described on the
following pages (combination for combination) for
Outdoor unit.
11
Described at pages before: Detailed Setting Procedure
for Remote Controller Model CZ-RTC2 / CZ-RTC4
12
After restart Power supply and Initialisation is finished,
proceed commissioning.
Check Indoor Unit
Turn Power “ON”
Start Indoor Unit Detail Setting
Set Indoor Unit
"DN" code 10 & 11
Start Outdoor Unit Detail Setting
Restart Detail Setting and set
other Indoor Unit "DN" codes
Set Outdoor Unit "DN" codes
Finish Indoor Unit
"DN" code setting
Finish Outdoor unit
"DN" code setting
Reset Power supply
Initialization
Initialization