3.2.14 Surge Protector Installation
CAUTION
Performing surge protection is essential. Make sure to follow the instructions in this section.
Overview
A massive electrical surge can be caused if lightning strikes a telephone cable 10 m above ground, or if a
telephone line comes into contact with a power line. A surge protector is a device that is connected to a trunk
to prevent potentially dangerous electrical surges from entering the building via the trunk and damaging the
PBX and connected equipment.
To protect the system from electrical surges, we strongly recommend connecting the system to a surge
protector that meets the following specifications:
–
Surge arrestor type: 3-electrode arrestor
–
DC spark-over voltage: 230 V
–
Maximum peak current: at least 10 kA
Additionally, proper earthing is very important for the protection of the system (refer to "3.2.5 Frame Earth
Connection").
Many countries/areas have regulations requiring surge protection. Be sure to comply with all applicable laws,
regulations, and guidelines.
Installation
Trunk
Trunk
Trunk
Earth
Surge
Protector
Extn.
Extn.
Extn.: Extension line
SLT
PT
PT-interface CS
CS
PBX
Frame
Earth
Terminal
Board
Installation Manual
79
3.2.14 Surge Protector Installation
Summary of Contents for KX-TDE200
Page 20: ...20 Installation Manual Table of Contents...
Page 172: ...172 Installation Manual 3 13 1 Starting the PBX...
Page 192: ...192 Installation Manual 5 1 5 Troubleshooting by Error Log...
Page 193: ...Section 6 Appendix Installation Manual 193...
Page 197: ...Index Installation Manual 197...
Page 203: ...Installation Manual 203 Notes...