4.2.4 Frame Ground Connection
KX-NS700/KX-NS720
1.
Loosen the screw.
2.
Insert a grounding wire (user-supplied).
3.
Tighten the screw.
4.
Connect the grounding wire to ground.
To ground
Screw
Grounding wire
WARNING
•
Proper grounding (connection to ground) is very important to reduce the risk to the user of
electrocution or to protect the PBX from the bad effects of external noise in the case of a
lightning strike.
•
The grounding wire of the AC cable has an effect against external noise and lightning strikes,
but it may not be enough to protect the PBX and to ensure electromagnetic compatibility. A
permanent connection between ground and the ground terminal of the PBX must be made.
CAUTION
For grounding wire, green-and-yellow insulation is required, and the cross-sectional area of the conductor
must be more than 0.75 mm
2
or 18 AWG.
Notice
Be sure to comply with applicable local regulations (e.g., laws, guidelines).
In most of the continental United States, the ground provided by the "Third wire ground" at the commercial
power outlet will be satisfactory. However, in a small percentage of cases this ground may be installed
incorrectly. Therefore, the following test procedure should be performed.
Test Procedure
1.
Obtain a suitable voltmeter and set it for a possible reading of up to 250 V AC.
2.
Connect the meter probes between the 2 main AC voltage points on the wall outlet. The reading obtained
should be 108 V AC to 132 V AC.
3.
Move one of the meter probes to the 3rd prong terminal (GND). Either the same reading or a reading of 0
volt should be obtained.
4.
If a reading of 0 volt at one terminal and a reading of 108 V AC to 132 V AC at the other terminal is not
obtained, the outlet is not properly grounded. This condition should be corrected by a qualified electrician
(per article 250 of the National Electrical Code).
5.
If a reading of 0 volt at one terminal and a reading of 108 V AC to 132 V AC at the other terminal is obtained,
then set the meter to the "OHMS/RX1" scale, place one probe at the GND Terminal and the other probe
at the terminal which gave a reading of 0 volt. A reading of less than 1 ohm should be obtained. If the
reading is not obtained, the outlet is not adequately grounded. See qualified electrician.
80
Installation Manual
Document Version 2016-03
4.2.4 Frame Ground Connection
Summary of Contents for KX-NS700
Page 152: ...152 Installation Manual Document Version 2016 03 4 13 Starting the PBX ...
Page 256: ...256 Installation Manual Document Version 2016 03 6 1 Methods of Stacking Expansion Units ...
Page 270: ...270 Installation Manual Document Version 2016 03 7 1 6 Troubleshooting by Error Log ...
Page 302: ...302 Installation Manual Document Version 2016 03 8 6 Port Security ...
Page 307: ...Document Version 2016 03 Installation Manual 307 Notes ...