KW1M-H Eco-POWER METER
39
5.5 Demand function
(Japanese demand)
A demand function is a function which presumes the average power for every 30 minutes time span,
and it judges for every minute.
This works demand monitoring for electric power input by CT or pulse. In order to use demand
monitoring by pulse input, input pulse that meet the specifications of 8.2.3.
It outputs demand alarm according to the setting conditions.
Please use this simple demand function as your standard. The value is not guaranteed.
Caution
(1)Definition of demand
It is demand measurement in order to use by yourself as your standard.
(2) The time used by this function is the time set up with Eco-POWER METER.
Therefore, it is different from the demand meter controlled by an electric power company.
◆
Output demand alarm and Display demand alarm
When present demand or estimated demand exceeds the demand setting value, it output and it
displays.
[Present demand or Estimated demand
≧
Demand setting value]
It keeps alarm output and alarm indication for 1 minute, after that,
[Present demand or Estimated demand
≧
Demand setting value] -> Keep alarm
[Present demand or Estimated demand
<
Demand setting value] -> Clear alarm
When you set the hysterisis with demand alarm setting mode 2, the timing of clear alarm is as below.
Ex.) Demand setting value: 100kW Hysterisis: 10%
When the present demand or the estimated demand exceeds 100kW, it output alarm and keep
the alarm for 1 minute. After that if the current demnd or the estimated demand exceeds 90kW, it
keep the alarm. If it is below 90kW, it clears alarm.
When you set the hysterisis, it can avoid frequent alarm output ON/OFF near a demand target
value.
【
Alarm output
】
・
It output with pulse output terminal.(open collector)
・
It output only when ‘DEM’ is set with unit for pulse output setting mode.
・
It doesn’t output alarm if demand setting value is set to ‘0.00’kW.
【
Alarm indication
】
・
’d’ is blinking on the bottom line of the display.
・
It indicates ‘d’ when the present demand or the estimated demand exceeds the setting value,
regardless the setting of unit for pulse output setting mode.
・
It doesn’t output alarm if demand setting value is set to ‘0.00’kW.
Lighting OP.
indicator
Blinking ‘D’