DA-PU100 Series Administrator's Manual
20
2.4.2
Connection of power supply
Follow this procedure to wire the product to the distribution box.
1. Remove the terminal cover.
•
Use a Phillips screwdriver to remove the terminal cover fixing screw.
2. Wire L phase of the power line to terminal L(
①
) and N phase to terminal N(
②
).
•
Connect the L phase terminal (
①
) and N phase terminal (
②
) correctly.
•
Applicable AWG value is 20 - 14. Use certified or equivalent wires for the electric wires of this
product.
Diameter (single wire): 0.813 mm to 1.628 mm
Cross section (stranded wire): 0.519 m² to 2.081 m²
•
When using a single wire, please strip off 8 mm of the coating.
•
When using stranded wire, use Y type crimp terminal with insulation tube (M4).
•
The proper tightening torque is 1.6 N·m to 1.8 N·m. Please tighten the screw securely.
•
Make sure there is no biting in the coating of the wire, such as a terminal washer.
•
Connect the electrical wiring correctly according to the specifications of the distribution board.
3. Attach the terminal cover
Summary of Contents for HD-PLC DA-PU100
Page 1: ...Administrator s Manual PLC Adaptor Model No DA PU100 ...
Page 4: ...DA PU100 Series Administrator s Manual 4 Chapter 1 Introduction ...
Page 9: ...DA PU100 Series Administrator s Manual 9 Chapter 2 Installation and Operation ...
Page 25: ...DA PU100 Series Administrator s Manual 25 Chapter 3 PC Tools ...
Page 32: ...DA PU100 Series Administrator s Manual 32 Chapter 4 Preparation for Operation ...
Page 58: ...DA PU100 Series Administrator s Manual 58 Chapter 5 Troubleshooting ...
Page 62: ...DA PU100 Series Administrator s Manual 62 Chapter 6 Specifications ...
Page 65: ...DA PU100 Series Administrator s Manual 65 7 Dimensions With the fixing brackets attached ...