Installation and Wiring
FP
Σ
User's Manual
74
6.1.5 Connecting FP0 Expansion Units
The expansion units are connected to the right side of the CPU. Use the expansion connector
and the expansion hooks on the side of the unit.
1.
2.
3.
Procedure
1. Peel seal on right side of the unit to expose expansion connector
2. Raise expansion hooks on top and bottom of the unit
3. Align pins and holes in all four corners
4. Insert pins into holes so that there is no gap between units
5. Push expansion hooks back into place
You can now add up to two more units in the same manner.
Summary of Contents for FPS Series
Page 7: ......
Page 17: ......
Page 18: ...Chapter 1 Safety Measures...
Page 21: ......
Page 22: ...Chapter 2 Overview...
Page 32: ...Chapter 3 CPU Types...
Page 47: ...CPU Types FP User s Manual 30 LD Body...
Page 51: ...CPU Types FP User s Manual 34 POU Header and LD Body...
Page 55: ...CPU Types FP User s Manual 38 LD Body...
Page 57: ......
Page 58: ...Chapter 4 Expansion...
Page 73: ......
Page 74: ...Chapter 5 I O Allocation...
Page 81: ......
Page 82: ...Chapter 6 Installation and Wiring...
Page 115: ......
Page 116: ...Chapter 7 High Speed Counter and Pulse Output...
Page 169: ......
Page 170: ...Chapter 8 Communication...
Page 227: ...Communication FP User s Manual 210 LD Body ST Body...
Page 233: ...Communication FP User s Manual 216 POU Header LD Body...
Page 236: ...FP User s Manual 8 6 Program Controlled Communication 219 POU Header LD Body 1 2...
Page 237: ...Communication FP User s Manual 220 2 2 ST Body...
Page 266: ...Chapter 9 Security Functions...
Page 273: ......
Page 274: ...Chapter 10 Other Functions...
Page 277: ......
Page 278: ...Chapter 11 Troubleshooting...
Page 289: ......
Page 290: ...Chapter 12 Appendix...