Operation Manual
FT128 Rev 2.4
85
20 Perform Monthly Test (H1)
The FT128 and the building must be tested on a regular basis, please refer to the
Australian maintenance standard AS1851 for details regarding monthly, quarterly and
annual test.
In test mode, only the alarm points are tested, i.e. no outputs (no sounders) will be
activated during the test. (Alarm devices can be tested via menu H8/S6).
If a real fire alarm is activated by
an alarm point
not
in test mode
, the normal fire alarm
functions will be activated, i.e. fire alarm presentation, outputs (sounders) activated,
routing equipment (Fire Brigade TX) activated, etc.
Note: If FT128 door is left open, the output(s) for external strobe or alarm bell might be
disabled (if set in EBLWin).
There will be an automatic termination of the test mode one hour after the latest tested
alarm point / zone.
See also chapter "Perform ZONE TEST (test mode) (H7)
"
, page 121.
Action
Text in display
Comments
"Access"
Log on to FT128 as shown
in page 35.
Perform monthly test
ACCEPT? H1
"A"
Check that all LEDs light up!
ACCEPT
"A"
▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒
▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒
The buzzer (in FT128)
sounds and all dots in the
display are shown. All
LEDs light up, including
LEDs in units connected
via I/O Matrix board 4582.
"A"
Zones to be set in TEST MODE:
? ? ?? ?? ?? Start test: ACCEPT
Write zone
numbers e.g. 01,
02, 03, 04)
Zones in test mode:
01 02 03 04 Start test: ACCEPT
Press "A" to start the test
mode.
"A"
Zones in test mode:
01 02 03 04 End test: ACCEPT
LED "Test mode" (L9) will
light up. Perform the tests.
The zone(s) will stay in test mode until the test mode is terminated
.
The test mode is terminated in this
menu or automatically one hour after the latest test alarm. This is valid for each zone respectively.
Perform the test as quickly as possible, since the output(s) for routing equipment (Fire Brigade TX) are disabled
during the test mode. Also, the parts of the zones in test mode, not visible for the test personnel, are disabled.
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled", i.e.
fire alarm will be detected faster than normal.
In the tested alarm point, the LED will light up for approximately 10 seconds, then the alarm point will be
automatically reset. There will be a test mode alarm indication in the FT128 display. The printer, if available, will
print out every tested alarm point (Zone: xxx Address: xx Time: HH.MM).
A detector in test mode will not be able to activate fault.
Zones 01 in test mode
More…
You are no longer in menu
H1 but still in test mode.
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...