Operation Manual
FT128 Rev 2.4
58
15 Alarm Reset
Note: The alarm “RESET” button will not function unless the programmed alarm devices
have been silenced i.e. “Silence alarm devices” button is activated.
15.1
Pre-Warning Reset
Pre-warning is non-latching i.e. resets automatically when the alarm point / zone is no
longer above pre-warning level. Outputs activated by pre-warning will be de-activated.
15.2
Fire Alarm Reset
In the New Zealand convention,
fire alarms
are shown in the LCD as normal fire alarms
with “
ALM
”, acknowledged alarms shown with “
ACK
” and isolated alarms shown with
“
ISO
”.
Note: The detectors having activated fire alarms after reset, must be inspected, tested
and replaced when required.
One of the following alarm reset alternatives is valid. This is selected via EBLWin. "All" is
default.
15.2.1
All (default)
All activated fire alarms (alarm points / zones) will be reset by pressing "RESET"
(P4) once but must be preceded by “Silence alarm devices” button (P3) activation
(this is in accordance with the fire brigade standard AS4428.3:2010).
The push button has to be pressed for minimum 0.5 sec.
When all fire alarms are reset
, LEDs "FIRE" (L1) and "Alarm Queued" (L2) are turned
off. If there are other conditions exist e.g. fault condition, the corresponding information
will be shown (fault message), for the priority order see section 3.4.2.2 “Information
Priority Order” page 19.
All outputs (for fire alarm) are reset, i.e. de-activated.
Note: When "Single" or "Single with automatic disablement" is used, all alarms can be
reset by pressing "RESET" (P3) and approx. 0.1 sec. later also press "Enter" and hold
them pressed for > 0.5 sec.
Both alternatives must not be used in the Australian or
NZ conventions
.
15.2.2
Single
Each fire alarm (alarm point / zone) has to be reset individually.
Press "Reset" (P4) to reset the fire alarm currently shown to the left in the display.
The push button has to be pressed for min. 0.5 sec.
Output(s) programmed for that fire alarm (alarm point / zone) will be reset, i.e. de-activated.
If more than one fire alarm is activated (i.e. LEDs "Alarms queued" (L2) are lit) the next fire
alarm in the queue will be shown in the display. It has to be reset same as the first one.
When all fire alarms are reset, LEDs "Fire" (L1) and "Alarms queued" (L2) are turned off.
If there are other conditions (e.g. a fault condition) the corresponding information will be
Summary of Contents for Firetracker FT128
Page 1: ...Operation Manual FT128 Rev 2 4 For Software V2 4 x FT128 FDCIE MA350 April 2018 ...
Page 2: ...2 This page has deliberately been left blank ...
Page 33: ...Operation Manual FT128 Rev 2 4 33 Figure 25 Field Module Enclosure BAFMES ...
Page 144: ...Operation Manual FT128 Rev 2 4 144 Figure 26 FT128 General Arrangement for 19 Rack System ...
Page 145: ...Operation Manual FT128 Rev 2 4 145 Figure 27 FT128 Standard Block Wiring Diagram ...
Page 146: ...Operation Manual FT128 Rev 2 4 146 Figure 28 NZFT128 Block Wiring Diagram for NZ ...