62
Operation Manual
FT1020G3 Rev 2.10.4
Note:
The "Ackn. alert annunciation" text is only visible if an AA alarm is activated.
15.5
Key Cabinet Alarm
In some European conventions, the fire brigade personnel use a key cabinet to store a key
for the building.
This feature is not used in AU or NZ conventions
.
15.6
Co-Incidence Alarm (2-Address / -Zone Dependence)
The co-incidence alarm function is programmed via EBLWin for specific alarm points /
zones.
When only one
zone
or one
zone / address
(alarm point) is in alarm state, the FDCIE
buzzer sounds (0.8 / 5 sec.) and there is a
Co-incidence alarm
presentation in the display.
Note
: LEDs "Fire" (L1) are not indicating a co-incidence alarm.
The co-incidence alarm will be automatically
Reset
after 5 minutes or via the "Reset" button
(P3). See chapter "Alarm reset", page 68.
Example; Co-incidence alarm zone 123, address 45 (within zone 123):
If more than one Co-incidence alarm
not
dependent on each other are activated, the LEDs
"SEVERAL ALARMS" (L6) are blinking and the Co-incidence alarms will be automatically
scrolled (each 5
th
second).
If
two or more zones
or
alarm points
(zone / addresses) dependent on each other are in
alarm status at the same time, normal fire alarm (see above) will be activated in the system.
The co-incidence alarm function can be turned on / off via a time channel.
Fire alarm: 010-01
Alarm
number 1 (of
1)
Alert annunciation
010-01
SMOKE
User definable alarm text for 010-01
Zone
Addres
s
1 zone in
alarm
Menu
Ackn. Alert
annunciation
CO-incidence alarm
123-45
SMOKE
User definable alarm text for 123-45
Zone
Addres
s
Menu
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...