169
Operation Manual
FT1020G3 Rev 2.10.4
32
FDCIE Maintenance
The FDCIE shall be maintained and tested in accordance with the Australian standard
AS1851.
To avoid the Fault TX output(s) to be activated, they can be disabled via menu H2/B5 (or
via an open door, see chapter "Open door” page 56. However, in Australia the routing
equipment
must
be isolated via the ASE.
Regarding the fault condition, see chapter "Fault", page 71 and "Fault messages", page 72
Note:
Most of the faults have approximately 60 seconds delay.
Each control unit should be tested as follows:
•
Perform monthly / quarterly / yearly test (menu H1).
•
Remove one battery fuse (e.g. F2 on the Main board 5012). The following fault
message will be shown within one minute:
FAULT: Battery not connected CU xx
NOTE! xx is depending on control unit (xx=00-29).
•
Re-place the fuse and acknowledge the fault (menu H6).
•
Check the manual call points on the panel door. Take required measures. Use
the manual call point test key to activate fire alarm.
•
Check some control outputs. Are they activated according to programmed control
expressions?
32.1
Replacing a TLON Connection Board and/or the Main Board
In a TLON network programming, some unique data is stored in a memory on the 5090
TLON connection board and some stored in a memory on the main board.
Note
: The main board 5012 is not compatible with the old TLON connection board 1590.
Replacing only a TLON connection board 5090
After replacing the board:
•
In TLON Manager version 1.2 do "Replace", "Update" and "Save".
•
In TLON Manager version ≥ V2.0 do "Replace" and "Update" ("Save" is
automatically done).
Replacing both a TLON connection board 5090 and also the Main Board
After replacing the boards:
•
In TLON Manager version 1.2 do "Replace", "Update" and "Save".
•
In TLON
Manager version ≥ V2.0 do "Replace" and "Update" ("Save" is
automatically done).
Replacing the Main board
After replacing the main board, mount the TLON connection board(s) in the same position
as on the replaced main board:
•
In TLON Manager version 1.2 do "Update" and "Save".
•
In TLON Manager version ≥ V2.0 do "Update" ("Save" is automatically
done).
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...