INSTRUCTION MANUAL
Simple Wire-saving Unit for Leak Detection Sensor
EX-FC1
MJE-EXFC1 No.0052-90V
Thank you very much for purchasing Panasonic products.
Please read this Instruction Manual carefully and thoroughly for the correct
and optimum use of this product.
Kindly keep this manual in a convenient place for quick reference.
In case of using sensing devices for prevention of accidents etc. which
damage a human life or properties, be sure to construct the system so
that all of the machinery operates to the safety side. This product itself
does not posses control functions needed for accident prevention or
safety maintenance.
OUTLINE
1
●
This is the simple wire-saving unit which can be connected with max. 8
leak detection sensors.
●
Even if only one leak detection sensor is connected to this product, the out-
put is gained when leak is detected or the sensor is mounted improperly.
●
Since the exclusive snap
male connector (
SL-CP1
) is used for connec-
tion, wire-saving can be easily made.
MOUNTING
3
●
In case of using screws
•
Mount using M4 pan head screws
with a tightening torque of 0.8N·m
or less. However, in case of side
mounting, make sure to mount the
unit such that the unit stopper faces
front.
Mounting position 1
●
Two installation positions are available for the unit mounting base so that
the unit direction can be changed. Install the base at one of them.
Mounting position 2
Unit
Unit mounting base
Din rail stopper
7
6
5
4
3
2
1
0
Unit
Unit mounting base
DIN rail stopper
●
In case of using a DIN rail or the
mounting bracket (MS-DIN-3)
(optional).
1. Fit the rear part of the unit mount-
ing base on a 35mm width DIN rail
or the mounting bracket (
MS-DIN-3
)
(optional).
2. Press down the front part of the
unit mounting base on the 35mm
width DIN rail and fit the front part
of the base on the DIN rail.
* For removal, insert a flathead
screwdriver into the DIN rail stop-
per and pull towards yourself.
1
2
DIN rail stopper
35mm width DIN rail or the mounting
bracket (
MS-DIN-3
) (Optional)
Flathead screwdriver
DIN rail stopper
Unit stopper
Unit
Unit mounting
base
M4 pan head screw
Please arrange
separately.
●
When mounting the unit, be sure to use the unit mounting base
(
MS-SL-2
) (accessory).
●
When installing the unit mounting base to the unit, insert the base
aligned with the grooves of the unit and move until the unit stopper is
locked.
Grooves
Unit stopper
1. Insert aligned with the
groove of the unit.
2. Make the unit stopper
locked.
I/O CIRCUIT DIAGRAM (for 1 channel)
4
Note: Since the output does not incorporate a short-circuit protection circuit, make sure to use
this product within the specification and take care against wrong wiring.
12 to 24V DC±10%
Main circuit
Sensor side
Internal circuit
Users’ circuit
IN
*1
No
connection
0V
Terminal No.
(Brown) 12 to 24V DC±10%
(White) OUT
(Black) OUT
Relay contact
(1a contact)
(Blue) 0V
Color code
* 1
Non-voltage contact or NPN open-collector transistor
(amplifier built-in leak detection sensor)
or
PART DESCRIPTION
2
2
1
4
3
5
Designation
Function
1 Normal indicator
(Green × 8)
Lights up when sensors are connected to each channel
and the connection setting switch is set to ON.
2 Error indicator
(Red × 8)
Lights up when leak is detected by any sensor con-
nected or any sensor is mounted improperly.
For details, refer to “
CONNECTION SETTING
SWITCH
.”
3 Output indicator
(Orange)
Lights up when the output relay is ON (Normal).
4 Connection setting
switch
Set the switch to ON when the leak detection sensor is
connected, set to OFF when the leak detection sensor
is not connected.
5 Connector
Connect the leak detection sensors.