ELC500 Control unit
22
Cabling of Power Supply for ELC500
3.2.2
For using by supplying 24V DC to ELC500, wire the power supply cable according to the below.
Use power supply cable (attached unit: Model No. AFPG805)
Insert the power supply cable to power supply connector.
Note
Do not use the power supply cable when using the power supply unit.
■
Power supply voltage
Check that the connected power supply voltage is in the range of the allowable power supply.
Rated input voltage
Allowable voltage
Rated output capacity
24V DC
20.4 to 28.8V DC
24W or more
Note
When connecting GT series to GT power supply terminal (24V),
use within the range of 21.6 to 26.4V.
■
Power supply selection (Refer to 1.5)
Select a power supply with the capacity of equal to or larger than the capacity of the unit.
In addition, select a power supply of 24 W or more even in the minimum configuration.
To protect against abnormal voltage from the power supply line, Use an isolated type power supply
with built-in protection circuit. The regurator on the unit is no-insulation type.
When using the power supply without built-in protection circuit, be sure to use a protection element
such as fuse.