EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
95
29. SET CALENDAR AND CLOCK (H3)
The RTC component has a capacitor as a backup power supply. Normally, date, day of the week and time only have to be set when
the power is turned on the control unit for the first time. If required, the
clock might be corrected, so that the "time stamps" for fire alarms, faults, etc. will be correct.
The calendar and clock can be set in any c.i.e. for the whole system. Every day (at midnight) the calendar and clock will be syn
-
chronised.
a) Log on to the c.i.e.
b) Navigate to menu H3.
c) Press
. Depending on if it is the date, time and/or the day that shall be set, press and to highlight it.
d) Use the keypad to enter new values. Press
.
To exit the menu without making any changes, press ESC.
The capacitor can supply the RTC for a couple of days. When the power has been turned off, it is recom
-
mended to check / set the date and time in menu H3.