EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
89
28. DISABLE OR RE-ENABLE (H2)
a) Log on to the c.i.e.
b) Navigate to menu H2.
c) Press
. A sub menu list (B1 – B6) will be displayed.
A whole zone, one or more alarm points within a zone and/or control outputs can be disabled via menus H2/B1-B2. This function
can be used for temporary disablement (e.g. craftsmen working in the premises, etc.).
If the function Enhanced disablement is enabled (default), disabled alarm points cannot activate Pre warning, fire alarm and fault.
If this function is not enabled (via EBLWin), disabled alarm points cannot activate Pre-warning and fire alarm but fault can be gener
-
ated. (This is a violation to the EN54-2 standard.
An Addressable manual call point can be disabled (but shall normally not be disabled). However, when a whole zone is disabled, the
addressable manual call points will not be disabled for safety reasons. (This function can depend on convention / country.)
Up to 512 whole zones can be disabled via menu H2/B1.
Up to 200 alarm points (zones / address) can be individually disabled via menu H2/B1. (Alarm points disabled via time channels are
not limited and must not be counted!)
Up to 200 outputs can be individually disabled via menu H2/B2.
Disabled output will stay in (or return to) the normal condition for the output respectively. (Collectively disabled outputs via menus
H2/B3 – B4 are not limited and must not be counted!)
It is not possible to exceed the limits. A warning will be shown:
Don't forget to re-enable (via menus H2/B1-B2), or use automatic re-enablement for zones and alarm points.
Disablements are listed in menus H4/U1 & U2 from which it is also possible to get a print-out.
LED Fault / Disablements "General disablements" is indicating one or more disablements in the system.
Disablements are also shown in the display. An example:
See chapter "The information area priority order", page 24, regarding priority order.
Disablements (and faults) are indicated by a 2-sec. beep when you close the control unit door.
Zone 001 disabled
yyyy-mm-dd hh:mm
Zone 002 address 01 disabled
yyyy-mm-dd hh:mm
....
Number of disablements in system: 2
Max. disablements reached!
Disablement not performed