EBL128 Planning Instructions V2.0.x
119
The outside switch is turned OFF
(i.e. from activated to not
activated state).
The c.i.e. built-in buzzer is re-enabled.
The fault
"
FAULT: FB Silence switch active"
will be
Serviced
.
126
Any fire alarm ("ALM") and acknowledged alarm ("ACK") will
automatically be disabled / isolated. (I.e. it has to be re-
enabled via menu H2/B1.) Indicated by LED "Disablements".
Any fire alarm ("ALM") and acknowledged alarm ("ACK") will
automatically change the state to "Isolated alarm" (see below)
and in the fire alarm list (presented in the LCD) "
ALM
" or
"
ACK
" will be replaced with "
ISO
".
An example:
ISO
ZONE-ADDR 12-46 LAST ZONE 12 No. 01
This is a user defined alarm text.
14.1.2.1
Isolated alarm
A fire alarm will automatically change state to "Isolated alarm" when
the "outside switch" (see above) is turned OFF, i.e. when it is not
activated any more (see above).
The following is valid for an isolated alarm.
LED:s "Fire" (on the front) will not be activated.
The c.i.e. built-in buzzer will not be activated.
Presented as isolated alarm, see the example above (ISO ……).
Programmable outputs will not be activated.
Output for routing equipment (Fire brigade tx) will not be
activated.
14.2
Battery faults
For other conventions, see chapter "Security functions", page 168.
14.2.1
FAULT: Battery
The following battery check is performed:
The battery charging is turned off every 30
th
second.
Battery voltage is checked.
Battery voltage < 24.4 V generates a fault.
Fault message:
FAULT: Battery
14.2.2
FAULT: Low battery capacity
The following battery check is performed:
126
Since this fault is always latched, it has to be acknowledged via menu H6.