Minimum / Maximum sensor values
To find out how the environment is, where an analog detector 33xx /
430x / 440x
in NORMAL mode
is mounted, the
minimum and
maximum sensor values
can be studied. The sensor values are
continuously picked up and evaluated by EBL128 for each detector
individually. Every value is checked if it is a new minimum or
maximum value for that detector and if so, the value will be stored.
At midnight every day a memory will be updated and the new
minimum and maximum sensor values
99
can be read in menu H4/U3
or via EBLWin.
For analog smoke detectors the minimum and maximum sensor values
are shown as XX.X % (obscuration) per meter.
For analog heat detectors the values are shown as XX°C.
13.8
2-zone / 2-address dependence (Co-
incidence alarm)
In some premises 2-zone or 2-address dependent fire alarm ("Two unit
dependent" in EBLWin) can be used to avoid unwanted / false alarms
(nuisance alarms). A time channel can turn on/off this function.
13.8.1
2-zone dependence
Each zone in the system can be programmed to be "Two zone
dependent" for fire alarm activation. The zone has to belong to one of
ten "Two zone dependent" groups (1-10).
100
Function:
Two or more zones in the same group have to be in "fire alarm
state"
101
at the same time to activate fire alarm in the control unit.
When only one of the zones is in "fire alarm state" it is indicated in the
control unit (c.i.e.) as follows:
The buzzer sounds like for pre-warning (0.8 / 5 sec.).
In the c.i.e. LCD the following information is shown:
Co-incidence alarm zone ZZ
Programmable outputs can be activated by trigger condition "Two
Zone Dependent Fire Alarm" but no other outputs will be activated.
A co-incidence alarm can be manually reset ("Reset" button on the
front) and will be automatically reset 5 min. after it is no longer in
"fire alarm state" (i.e. below the fire alarm level).
99
I.e. the min. / max. sensor values are from the previous day.
100
See also chapter "Two zone dependence", page 152.
101
Fire alarm state is when a fire alarm normally would have been activated
in the c.i.e.