INSTRUCTION MANUAL

Separate type · digital sensor controller

DPC-L100

 Sereis

For liquid / gas

MJE-DPCL100 No. 0040-92V

Thank you very much for purchasing Panasonic products. 
Read this Instruction Manual carefully and thoroughly for the correct and optimum 
use of this product.
Kindly keep this manual in a convenient place for quick reference.

WARNING

 Never use this product as a  device for personnel protection.
 In case of using devices for personnel protection, use products which

meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel 
protection applicable in each region or country.

 The product for use inside Japan complies with Japanese Measurement

Laws. Avoid using the product model for outside of Japan within Japan.

1

PART DESCRIPTION

Notes: 1)  Attach the unit switch plate corresponds to the set pressure unit.

2)  The product for use inside Japan can be set only to “MPa” or “kPa.”

2

MOUNTING

 

 T h e   s e n s o r   m o u n t i n g   b r a c k e t

MS-DP1-6

 is available as an option. 

When mounting the sensor onto the
sensor mounting bracket, etc., the tight-
ening torque should be 0.5N·m or less.

 

 T h e   p a n e l   m o u n t i n g   b r a c k e t

MS-DP1-2

 (optional), as well as the

front cover 

MS-DP1-3

 (optional) are

also available.

 

 For mounting of the panel mounting

bracket, refer to the Instruction Manual 
enclosed with 

MS-DP1-2

.

3

CONNECTION OF PRESSURE SENSOR HEAD

 

 In case of initial set up or reset, select pressure range.

 

 incase changing pressure sensor head, check pressure range.

Connection method

1.

Insert the pressure sensor head cable into the
product’s connector area for the pressure sen-
 

Disconnection method

1.

Pressing the release lever of the pressure sen-
sor head cable, pull out the connector.

Note:  Do not pull by holding the cable without pressing the re-

lease lever, as this can cause cable break or connector 
break.

<Terminal pin arrangement>

Terminal pin No.

Terminal name

1

Sensor head supply voltage

2

Analogue input

3

0V

4

Not used

4

WIRING

Connection method

1.

Insert cable with connector 

 into

the product’s connector area for a power / I-O
 

Disconnection method

1.

Pressing the release lever of the cable with con-
nector, pull out the connector.

Note: Do not pull by holding the cable without pressing the release 

lever, as this can cause cable break or connector break.

<Terminal pin arrangement>

Terminal pin 

No.

Terminal name

Terminal pin 

No.

Terminal name

1

+V

4

Comparative output 1

2

Analogue voltage 
/ current output

5

Comparative output 2

3

0V

6

External input

Connector area for a 
power supply / I-O cable

Connector area for a 
pressure sensor head

Output 1 operation 
indicator 

Lights up when com-
parative output 1 is ON

Output 2 operation 
indicator 

Lights up when com-
parative output 2 is ON

Mode selection key

Set value UP key

Set value 
DOWN key

Attach area for 
unit switch plate
(Note 1, 2)

Main display

Sub display

Release lever

Pressure 
sensor 
head cable

<Connector area of the pressure sensor head cable>
e-con: 1473562-4
[Tyco Electronics AMP G.K.]

Release lever 

Cable with 
connector 

CN-66A-C

<Connector area of the cable with connector>
Housing: PAP-06V-S
[JST Mfg. Co., Ltd.]

M3 (length 6mm) 
screws with washers

Accessory with

 

MS-DP1-6

Sensor mounting bracket 

MS-DP1-6

 (Optional)

6

5

I/O CIRCUIT DIAGRAMS

NPN output type

PNP output type

     !"# $

2)  Take care that when the analogue current is output, 5V or more voltage generates. 
3)  When using the analogue voltage output, be careful to the input impedance of the connected device.

Furthermore, note that if the cable is extended, the cable resistance will cause the voltage to drop.

6

OUTPUT MODE AND OUTPUT OPERATION

 The EASY mode, hysteresis mode or window comparator mode can be se-

lected as the output mode for comparative output 1 and comparative output
2. Refer to <

Comparative output 1 / 2 output mode setting

> in “

MENU 

SETTING MODE

” for details.

EASY mode

 ON / OFF of the comparative output is controlled in this mode.

 %& $'

Refer to <

 

> in “

PRO MODE

” for setting.

 2) 

“ 

 ” is displayed for comparative output 1 and “ 

 ” for comparative output 2 on the sub-display. 

Hysteresis mode

 The comparative output ON / OFF state can be controlled with randomly set

hysteresis in this mode.

Notes: 1)  “ 

 ” or “ 

 ” is displayed for comparative output 1 and “ 

 ” or “ 

 ” is displayed for com-

parative output 2 on the sub display.

Window comparator mode

 

 In this mode, the ON or OFF state of the comparative output is controlled with

a pressure in the set range.

 %& $'

Refer to <

 

> in “

PRO MODE” for setting.”

 2) 

“ 

 ” or “ 

 ” is displayed for comparative output 1 and “ 

 ” or “ 

 ” is displayed  for com-

parative output 2 on the sub display.

* 8; = %&$; #

*1

Non-voltage contact, NPN transistor or 
DC 2-wire output

High (5 to 30V DC or Open): Invalid
Low (0.4V DC or less): valid

or

*2

Non-voltage contact, PNP transistor or 
DC 2-wire output

High (5 to +V DC or Open): valid
Low (0.6V DC or less): Invalid

or

Pressure

P

0

ON

OFF

Comparative 
output

H (Hysteresis)

%%&$@

Pressure

Hi

Lo

ON

OFF

H (Hysteresis)

H: 1 digit or more

When using psi unit model for out-
side of Japan, it is 2 digits or more. 
However, the 50MPa pressure 
range model is 20 digits or more.

Comparative 
output

Hi

Lo

ON

OFF

%%&$@

Pressure

Comparative 
output

H (Hysteresis)

H (Hysteresis)

(Gray) Analogue 
voltage / current 
output (Note 1, 2, 3)

(Brown) +V

(Black) Comparative output 1

(White) Comparative output 2

(Pink) External input

(Blue) 0V

12 to 24V DC
±10%

+

-

Load

Load

(*1)

Main circuit

(Brown) +V

(Pink) External input

(Black) Comparative output 1

(White) Comparative output 2

(Gray) Analogue 
voltage / current 
output (Note 1, 2, 3)

(Blue) 0V

Load

Load

(*2)

Main circuit

12 to 24V DC
±10%

+

-

Ramco National

800-280-6933 | [email protected]

www.panasonicsensors.com

Summary of Contents for DPC-L100 Series

Page 1: ...n indicator Lights up when com parative output 2 is ON Mode selection key Set value UP key Set value DOWN key Attach area for unit switch plate Note 1 2 Main display Sub display Release lever Pressure sensor head cable Connector area of the pressure sensor head cable e con 1473562 4 Tyco Electronics AMP G K Release lever Cable with connector CN 66A C Connector area of the cable with connector Hous...

Page 2: ...ressure range of pressure sensor head con nected to this product The set pressure range is memorized and the range is displayed every time after tuning on the power Then move to RUN mode In case replacing sensor head or resetting it set the pressure range again 8 RUN MODE Setting the threshold value Refer to Comparative output 1 2 output mode setting in MENU SETTING MODE for setting conditions The...

Page 3: ... hold 2 function Code 5th digit 6th digit 7th digit Displayed color of the main display Displayed color relation Response time Unit selection Note Display speed Eco mode Red when ON Comparative output 1 MPa 250ms OFF Comparative output 2 kPa std Green when ON Comparative output 1 kgf cm 2 Full Comparative output 2 5ms bar 500ms OFF Always red Comparative output 1 10ms psi std Comparative output 2 ...

Page 4: ...he sensor cable joint This sensor is suitable for indoor use only Avoid dust dirt and steam Take care that the product does not come in contact with water oil grease or organic solvents such as thinner etc Do not operate the keys with pointed or sharp objects Do not use this sensor in places having excessive vapor dust etc or where it may come in contact with corrosive gas etc Never disassemble or...

Reviews: