16
█
Precautions on using regenerative braking
· When using regenerative braking, set the parameter P026 to "0". Since the factory
setting is "1", the braking will not work.
█
Connected device, wire size and tightening torque
• 1-Phase 200V
Inverter
capacity
Rated
current
of circuit
breaker
(MCCB)
for wiring
Wire size
Screw
size
Tightening
torque
Braking resistor *1
L1, L2
U, V, W
Ground
wire
Allowable
braking
duty factor
Resistance
Allowable
continuous
power
0.2kW
10A
2mm
2
(AWG14)
2mm
2
(AWG14)
M3.5
(Ground
:
M4)
1.0 N · m
(Ground
:
1.2
N · m)
5%
120
Ω
80W
0.4kW
15A
0.75kW
20A
M4
1.2 N ·
m
1.5kW
30A
2.2kW
40A
3.5mm
2
(AWG12)
3.5mm
2
(AWG12)
80
Ω
120W
•3-phase 400V
Inverter
capacity
Rated
current
of circuit
breaker
(MCCB)
for wiring
Wire size
Screw
size
Tightening
torque
Braking resistor *1
L1, L2
U, V, W
Ground
wire
Allowable
braking
duty
factor
Resistance
Allowable
continuous
power
0.75kW
10A
2mm
2
(AWG14)
2mm
2
(AWG14)
M4
1.2 N · m
5%
470
Ω
80W
1.5kW
15A
5%
470
Ω
80W
2.2kW
20A
5%
320
Ω
120W
3.7kW
30A
5%
190
Ω
220W
5.5kW
50A
3.5mm
2
(AWG12)
3.5mm
2
(AWG12)
5%
117
Ω
340W
7.5kW
50A
3.5mm
2
(AWG12)
5%
95
Ω
440W
11kW
70A
8mm
2
(AWG8)
8mm
2
(AWG8)
M5
2.0 N · m
5%
63
Ω
660W
15kW
80A
14mm
2
(AWG6)
14mm
2
(AWG6)
5%
63
Ω
660W
*1) The above data is only for the reference of the condition with braking torque of
100%, maximum time of 5s and maximum braking duty factor of 5%.
Summary of Contents for AMK3000P22
Page 59: ...58 ...