Infrared Array Sensor

Grid-EYE Unit Type

AMGU4241

■ RS485 Communication line wiring

■ Terminal arrangement

■ Applicable cables

10 mm

32

ON

16 8 4 2 1

1 2 3 4 5 6

ON

1 2 3 4 5 6

ON

1 2

6

4 5

3

This product detects the presence of humans by

 

measuring the temperature 

distribution in the detection area and detecting the movement of objects that 

have a higher temperature than the background.

* A human body may not be detected when the difference between its surface 

  temperature and the room temperature is small.

Near the air outlet of an air 

conditioner, etc.

A place with highly reflective 

floor surfaces

A place with rapid temperature 

changes

A place with an automated moving

object

A place where the floor temperature

is high due to sunlight, floor heating, etc.

A place with swinging objects

Detection range (estimate) when the ceiling is 2.7 m high

3.6 m

1.6 m

100     mm

+5

0

+− +−

E

DC24V

(DC24V)

DC24V

OND

OND

E

+− +−

E

DC24V DC24V

OND

OND

E

DC24V GND

+ −

E E

DC24V GND

RS485

+ −

RS485 Termination

Model No.

Installation Instructions

Please make sure to read this manual before installation.

Safety Precautions

Please make sure to follow

Warning

Must be followed

● Insert cables deep enough for ensuring a wire connection.

    

Inadequate insertion may produce heat, causing burnout or fire.

Avoid installation in the following places.

Wiring Diagram

Power

supply

Power 

supply

Power 

supply

Control

device

Input    Feed    Termination

(Input)      (Feed)

(Input)         (Feed)

Termination side

D class grounding

D class grounding

Contact output

The termination-side device's 

feed and termination terminals 

must be connected to each other.

• Use shielded twisted pair cables.

• The shield must be grounded at one end. Ground terminals are for grounding only 

   

and require D class grounding.

• Use transition wiring for device connections. (Branch wiring not applicable)

Power cable

φ

0.65 to

φ

0.9 Cu (copper) Single wire only

RS485 signal cable

φ

0.65 to

φ

0.9 CPEV cable

Advance Check Items and Installation Requirements

1. Avoid incorrect wire connections and short circuits.
2. Wipe off stains using soft, dry cloth without scratching.
    Avoid using thinners, alkaline detergents, acid detergents, cleansers, 
    pesticides, etc. Their use may cause a failure.

Detection Range

How to Mount

RS485 Address Setting

Operation lamp

Illuminates red when a human

body is detected

Note: The detection range 

varies depending on the 

installation height.

● The ceiling height must be 2.7 m or lower.

   The product cannot be used on a sloped ceiling.

Depth above the ceiling 

surface: 50 mm or more

Claw part

Removal 

groove

* Check the detection 

  range after installation.

Area mask setting 

switch (4-bit)

Reset switch

Press the reset switch 

after setting changes.

Sensor

Ceiling board thickness: 

30 mm or less

Lower the fitting to fix by 

turning the screw with 

a Philips screwdriver.

* Remove the protection 

  film attached to the sensor 

  surface before mounting 

  the cover.

Note: Do not touch the 

          sensor surface.

Cover

Clamping metal fitting

How to Remove the Cover

Screwdriver

Binary numbers

Example of address setting

Removal groove

Turn right and left

Cover

Ceiling surface

Address setting switch 

(6-bit)

Address: 1

Address: 8

* Use binary numbers for address setting.