Technical Description 

1736 

Rev 1.0 

 

 

 

 

 

 

 

Alert Annunciation Unit  

1736 

S/W Ver. 1.4.x 

 

 

 

 

 

 

 

 

 

 

MA441    

 

 

 

 

 

 

 

 

 

 

August 2012

Summary of Contents for Alert annunciation unit 1736

Page 1: ...Technical Description 1736 Rev 1 0 Alert Annunciation Unit 1736 S W Ver 1 4 x MA441 August 2012 ...

Page 2: ...This page has deliberately been left blank ...

Page 3: ...texts _ 16 8 Commissioning of a new unit SSD download17 9 Restart _______________________________ 19 10 Fault messages ________________________ 21 10 1 Fault messages in the AA unit __________________ 21 10 2 Fault messages in the C I E ___________________ 21 10 2 1 System FT512 __________________________ 21 10 2 2 System FT128 __________________________ 22 10 2 3 System FT1020G3 _________________...

Page 4: ...D 12 Table 4 Current Consumption 30 List of Figures Figure 1 The Alert Annunciation Unit AAU 1736 6 Figure 2 The Alert Annunciation Unit AAU 1736 neutral front 10 Figure 3 Operation summary for the AA unit 1735 26 Figure 4 Alert Annunciation units 1736 Connections 27 Figure 5 1736 PCB position of terminal block J1 jumper JP8 27 ...

Page 5: ...cal and Operation Manuals for the system respectively The Alert annunciation unit 1736 shall run in SW mode 1736 1587 See also chapter General description page 6 This document is valid for the 1736 software version 1 4 x The Alert annunciation unit 1736 can be used in the systems FT512 FT128 and FT1020G3 In system FT1020G3 the 1736 software version 1 4 x must be used ...

Page 6: ... frequently used or not explained elsewhere in the document AA Alert Annunciation AAU Alert Annunciation Unit AA alarm Alert Annunciation alarm AA function Alert Annunciation function C I E Control and indicating equipment control unit C U Control unit Control and indicating equipment SW Software HW Hardware ...

Page 7: ...tion page 25 3 1 Alert Annunciation Unit 1736 Figure 1 The Alert Annunciation Unit AAU 1736 The Alert Annunciation Unit consists of a compact size enclosure made of grey RAL 7035 high impact ABS with temperature resistance up to 85 C Fitted with a supplementary O ring gasket it will comply with IP65 in respect of dust and moisture The unit has no door i e the front is accessed directly when requir...

Page 8: ...the main board connector J1 or via the termination board terminal 15 16 Australian convention but an optional RS485 transceiver component chip 4552 is required on the main board In system FT1020G3 1736 units running in SW mode 1736 1587 are connected directly to the main board connector J4 No additional interface required ...

Page 9: ...ands are available CU alternatives not valid for FT128 1 Control unit CU 2 Consecutive control units CU1 CU2 3 Zone zone 4 Consecutive zones zone1 zone2 5 Zone address zone addr 6 Consecutive zone addresses zone1 addr1 zone2 addr2 Explanations 1 CU Control unit number C I E no 00 29 2 CU1 The first control unit number in the sequence CU2 The last control unit number in the sequence 3 zone Zone num...

Page 10: ...Technical Description AAU 1736 Rev 1 9 Default for each AA unit is in system FT128 Zones 01 32 i e all alarms will be presented in all units ...

Page 11: ... annunciation function is enabled2 else turned off Buzzer is silent No text in the display and no back light No control button can be used 3 2 The AA function is normally enabled during daytime disabled during night time via a time channel 3 Press P5 Test for a test of the LEDs the buzzer and the display back light and dots NOTE This must be done only in quiescent condition Alarm queued Acknowledg...

Page 12: ... L3 Extinguishing Red Steady Outputs for Extinguishing are activated L4 Acknowledge Yellow Steady All AA alarms have been acknowledged by the push button P2 Acknowledge and new AA alarms will be automatically acknowledged L5 Fire brigade alerted Red Steady Output s for Fire brigade tx are activated 4 L6 Operation Green Steady The AA function is enabled Off The AA function is not enabled NOTE Regar...

Page 13: ... see chapter SW mode Address setting page 13 and regarding P3 chapter SW version page 23 Table 3 Buzzer and LCD Component Indicating Buzzer7 1 beep 5 s AA alarm Continuous All LEDs turned off as well A CPU memory fault in the unit Display All or selected Fire alarms AA alarms presented same as the C I E that the AA unit is connected to including a user definable text message alarm text if programm...

Page 14: ...It is factory set to Not selected and is hereby not addressed When a new AA unit is powered it will automatically be ready for the SW mode setting As an alternative an AA unit in operation8 can be ready for the SW mode setting via the jumper J4 in the unit See the following chapter When the AA unit is ready for the SW mode setting this is indicated by the LED L2 Alarms queued The back light is tur...

Page 15: ...an be changed to the following For an AA unit the address can be set to 00 15 11 Default is 00 Scroll to the required address with the push button P1 black Store the selected address with the push button P2 yellow and the unit will automatically restart and enter its normal operation mode 12 6 2 1 Address setting mode via the C I E A specific AA unit or all the AA units connected to the same line ...

Page 16: ...page is a flow chart showing the SW mode setting Address setting etc Power on Restart Reset via JP1 J4 ON Yes No Yes No Normal operation SW mode setting SW mode xxxx 1587 No Yes Address command from c i e Language setting Address setting SW mode selected J4 ON No No Yes Yes ...

Page 17: ...ead of the text messages sent out from the C I E The priority order is as follows 1 Point alarm text stored in the AA unit 2 Zone alarm text stored in the AA unit 3 Default alarm text stored in the AA unit 4 Text sent out from the C I E When alarm texts shall be stored in all or in some AA units the unique alarm texts are created in Win512 Win128 WinG3 and downloaded when the C I E site specific d...

Page 18: ...ll now be powered up 3 A brand new unit will automatically be ready for the SW mode setting 4 After SW mode and address setting press P2 yellow and the unit will restart see chapter Restart page 19 5 Since the SSD is not downloaded in the C I E there will be a fault message in the unit s display No contact with Control unit All LED s in the unit will be turned off 6 Now the SSD have to be download...

Page 19: ...rogress 8 After download of SSD to an AA unit the following will be shown in its display very quickly SSD Download Memory OK or SSD Download Memory Fault Then the AAU will restart see chapter Restart page 19 9 The unit will then start working in normal operation mode ...

Page 20: ...memory OK All LEDs will be turned ON during the restart If there is a program memory fault a fault message will be shown in the display Memory fault in program area n n 1 or 2 The AA unit will not work A fault message will also be shown in the C I E In system FT512 FAULT Comm AAU xx 1587 board x CU xx In system FT128 FAULT No reply AAU x In system FT1020G3 FAULT No reply alert annunciation unit co...

Page 21: ...1 20 There will also be a fault message in the C I E In system FT512 FAULT SSD AAU xx 1587 board x CU xx In system FT128 FAULT Site specific data SSD AAU x In system FT512 G3 FAULT Site specific data alert annunciation unit control unit ...

Page 22: ... download see chapter Commissioning of a new unit SSD download page 17 Memory fault in program area n See chapter Restart page 19 10 2 Fault messages in the C I E 10 2 1 System FT512 FAULT 1587 board x CU xx Fault on no communication to the 1587 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT Comm AAU xx 1587 board x CU xx The cont...

Page 23: ...age 19 10 2 3 System FT1020G3 FAULT No reply alert annunciation unit xx control unit xx The contact with the external AAU is interrupted Check the cable and all connections Is a correct complete SSD download via WinG3 performed Check the address setting SW mode setting etc See also chapter Restart page 19 FAULT Alert annunciation unit xx The AAU is programmed via WinG3 as another type of unit or t...

Page 24: ...k Address XX Store Yellow press push buttons P1 black and P2 yellow simultaneously and the following will be displayed Rst nn Addr aaaaaaaa Version V vvvv Return Yellow Erase SSD Black nn restart type code and aaaaaaaa memory address before restart nn 00 Power On Reset Power supply connected nn 01 Watchdog Reset nn 02 Accidental jump to reset vector nn 03 External reset caused by external watchdog...

Page 25: ...elect Download program and select the SW file to be downloaded i e DU_version BIN where version is the valid program version e g 14x program version 1 4 x Check set the port and baud rate See also the Win512 Win128 WinG3 help 2 Connect the PC to the AA unit J2 3 Put the jumpers JP3 and JP4 in position A 4 Put the jumper JP2 BOOT in position 5 Put the AA unit in bootstrap mode i e put the jumper JP...

Page 26: ...operation summary for the Swedish version of the Alert Annunciation unit 1735 It is applicable to the English version 1736 See also chapter SW mode Address setting page 13 AA alarm acknowledged in any Alert Annunciation unit will be indicated in all Alert annunciation units AA alarm reset in any Alert annunciation unit or in the C I E will also be reset in all other Alert Annunciation units NOTE T...

Page 27: ...nical Description AAU 1736 Rev 1 26 Figure 3 Operation summary for the AA unit 1735 Note The AA unit 1736 is same as 1735 but it also has an LED Extinguishing and push buttons Silence alarm devices and Test ...

Page 28: ...nnunciation units 1736 Connections The connections to the terminal block J1 The jumper JP8 only has to be on place shunted if the unit is the last unit on the line NOTE The AA units 1736 can in FT512 only be connected to a 1587 board In FT128 24 V 0V S0 S1 to terminal block J1 13 14 15 16 In FT1020G3 24 V 0V S0 S1 to terminal block J4 35 36 37 38 Figure 5 1736 PCB position of terminal block J1 jum...

Page 29: ... used in this unit J10 Not used in this unit J11 Not used in this unit JP1 Reset Restart of the unit JP2 Boot The unit has to be in bootstrap mode before SW download JP3 Pos A PC for SW download connected via J2 Pos B The unit is connected to the C I E default JP4 Pos A PC for SW download connected via J2 Pos B The unit is connected to the C I E default JP8 Used when the unit is the last unit on t...

Page 30: ...JP8 JP8 mounted the termination resistor is connected 14 2 1 Cable The cable to be used in systems FT512 and FT1020G3 should be Twisted Pairs 2 x 2 x 1 mm2 screened tinned copper braid Cable length up to 1200 m theoretically depending on the cable type but the cable length is also dependent on the current consumption i e the type and number of units connected For more details regarding cable type ...

Page 31: ...following table shows the current consumption in relation to the actual line voltage min and normal respectively Table 4 Current Consumption Unit Current consumption Quiescent mA Active mA 12 V DC 24 V DC 12 V DC 24 V DC AA unit 1736 48 26 79 42 ...

Page 32: ...31 15 Revision history Issue Date Description Software revision Written By Checked By Initial 15 8 2011 Original Panasonic issue MEW01295 Rev 2 V1 4 Jan Patterson 1 0 20 8 2012 Change Panasonic issue to suit AU NZ Market V1 4 Anis Shenouda ...

Page 33: ...This page has deliberately been left blank ...

Page 34: ...3134 Ph 03 9879 5294 Fax 03 9879 5249 SA 729A Port Road Woodville SA 5011 Ph 08 8347 0000 Fax 08 8347 0600 QLD 2 49 Boyland Ave Coopers Plains QLD 4108 Ph 07 3373 8222 Fax 07 3373 8022 New Zealand Unit 106 the Zone 23 Edwin Street Mt Eden Auckland 1024 Ph 64 9 638 4644 Fax 64 9 638 4644 Toll Free NZ only 0800 220 007 WA Ph 0416 204 431 OR NATIONAL SALES NUMBER 1300 65 8000 FOR THE COST OF A LOCAL ...