Settings
KW2M-A/X User's Manual
45
5.5.5 Settings for Pulse Output
The measurement value of main unit CH1 is used fo for pulse output CH1 and the measurement value of
main unit CH2 is used for pulse output CH2.
[Integral power pulse]
Item
Description
1
Select CH *
Select channel to set.
2
Output type
Select pulse output type.
< List >
Integral power pulse, Alarm, General output
(initial: Integral power pulse)
3
Unit for output
Set unit used for pulse output.
< List >
0.001, 0.01, 0.1, 1, 10, 100kWh (initial: 0.001)
4
Direction
Select direction of power (import or export) to be used as a
threshold for pulse output.
< List >
P, -P (initial: P)
5
Target phase
Select a phase to monitor in order to judge the output.
Select
‘
Total
’
for measuring 3P3W.
< List >
Phase1, Phase2, Phase3, Total (initial: Total)
6
Pulse width
Set pulse width.
< Range >
1 to 100ms (initial: 1)
1
2
3
4
5
6