Settings
30
KW2M-A/X User's Manual
5.4.2 Settings for communication (RS485)
Protocol
Select serial communication protocol for main unit (RS485).
*When you change the protocol setting, the settings for device number, transmission speed (baud rate),
transmission format, stop bit and response time will be initialized.
M
- 1
C O M
R S 4 8 5
P r o t o c o l
M E
W
T O C O L
Press <ITEM/
>
>, <SHIFT/
∧
> to select.
[Set list]
MEWTOCOL, MODBUS(RTU) (initial: MEWTOCOL)
Device number
Set an individual device number for each unit when two or more units are connected to
communicate via serial communication (RS485).
M
- 1
C O M
R S 4 8 5
N o
9 9
Press <ITEM/
>
>, <SHIFT/
∧
> to set a value.
The setting range differs according to the protocol.
[Set range]
MEWTOCOL: 1 to 99
MODBUS(RTU): 1 to 247
Increase
Decrease
Transmission speed (Baud rate)
Select the transmission speed for RS485 communication.
Both the KW2MA and the communication partner (PLC etc.) must use the same setting.
M
- 1
C O M
R S 4 8 5
S p e e d
3 8 4 0 0 b p s
Press <ITEM/
>
>, <SHIFT/
∧
> to select a transmission
speed.
[Set list]
2400,
4800,
9600,
19200,
38400,
57600,
115200 [bps]
(initial: 19200)