7
・
When input voltage is under 5% of rating, it displays “0.0” and doesn’t measure.
(“Under 5%” means the value getting from this calculation “rated voltage 200(400) x 0.05 x VT ratio”.)
・
When input voltage exceeds 150%F.S. at each range,
「
‐
‐
‐
‐
‐
‐
」
will be displayed.
・
Voltage measurement parts
Eco-POWER METER measures the voltage as below.
<AKW1111 (400VAC applicable type)>
Display
System
R-V / RS-V
S-V / RT-V
T-V / TS-V
Single-phase two-wire
R-voltage (P1-P0)
(line voltage)
(Skip) (Skip)
Single-phase three-wire
R-voltage
(phase voltage)
(Skip)
T-voltage
(phase voltage)
Three-phase three-wire
RS-voltage (P1-P0)
(line voltage)
RT-voltage(P1-P2)
(line voltage)
TS-voltage (P2-P0)
(line voltage)
Three-phase four-wire
R-voltage
(phase voltage)
S-voltage
(phase voltage)
T-voltage
(phase voltage)
<AKW1110>
Display
System
R-V / RS-V
T-V / TS-V
Single-phase two-wire
R-voltage (P1-P0)
(line voltage)
(Skip)
Single-phase three-wire
R-voltage
(phase voltage)
T-voltage
(phase voltage)
Three-phase three-wire
RS-voltage (P1-P0)
(line voltage)
TS-voltage (P2-P0)
(line voltage)
3.2.5 Electricity Charge
It displays the standard electricity charge for the integrated electrical power.
・
Press <ITEM>key to display the electricity charge.
Sample
*
When the value exceeds ‘999999’,
「
‐
‐
‐
‐
‐
‐」
will be displayed.
3.2.6 Carbon dioxide conversion value
It displays the standard conversion value for the integrated electrical power.
・
Press <ITEM>key to display the conversion value.
Sample CO
2
conversion value (kg-CO
2
)
*
When the value exceeds ‘999999’,
「
‐
‐
‐
‐
‐
‐」
will be displayed.