If the voltage is properly applied to the load, there is probably an abnormality in the load.
If the voltage is not applied to the load, there is probably an abnormality in the output
section of the unit.
4.
Using the GM Programmer, check the monitor function by forcibly setting or resetting the
output.
If the output LED of the unit changes, it is possible that the output has been overwritten in
the program.
If the LED does not change, there is probably an abnormality in the output section of the
unit.
9.3.5 Desired Input Is Not Obtained: Checking when the Input Does Not Turn
ON / OFF
■
Condition
Both software factors such as program or I/O allocation and hardware factors such as wiring or
power supply can be assumed.
■
Solution
1.
If the input display LED is unlit, proceed to the following step. If it is lit, proceed to step 4.
2.
Recheck the wiring of the input devices for loose terminals, etc.
3.
Check if the voltage is properly applied to the input terminals.
If the voltage is properly applied to the input terminals, there is probably an abnormality in
the unit’s input part.
If the voltage is not applied to the input terminal, there is probably an abnormality in the
power supply or the input device.
4.
Using the GM Programmer, monitor the input state.
If the monitored state is OFF, there is probably an abnormality with the input unit.
If the monitored state is ON, there is probably an abnormality with the program.
9.3.6 If the ALARM LED Is Lit on the Expansion Unit
■
Condition
If the ALARM LED is lit on the expansion unit, there may be a system failure.
■
Solution
1.
Turn the system OFF and then ON.
2.
If the system is not reset, there may be a hardware failure. Please consult your Panasonic
representative.
9.3 What to Do If an Error Occurs
9-6
WUME-GM1H-02
Summary of Contents for AGM1CSEC16P
Page 1: ...Motion Controller GM1 Series Reference Manual Hardware WUME GM1H 02 2021 8 ...
Page 2: ... MEMO 2 WUME GM1H 02 ...
Page 4: ... MEMO iv WUME GM1H 02 ...
Page 8: ... MEMO viii WUME GM1H 02 ...
Page 12: ... MEMO 1 4 WUME GM1H 02 ...
Page 39: ...3 2 Expansion Units WUME GM1H 02 3 19 ...
Page 40: ... MEMO 3 20 WUME GM1H 02 ...
Page 70: ... MEMO 6 6 WUME GM1H 02 ...
Page 75: ...8 Device Reset 8 1 Device Reset by GM1 Controller Operation 8 2 WUME GM1H 02 8 1 ...
Page 84: ... MEMO 9 8 WUME GM1H 02 ...
Page 85: ...10 Maintenance and Inspection 10 1 Inspection 10 2 WUME GM1H 02 10 1 ...
Page 117: ...Pulse Output Unit Unit mm 11 6 Dimensions WUME GM1H 02 11 31 ...
Page 118: ... MEMO 11 32 WUME GM1H 02 ...
Page 122: ... MEMO App 4 WUME GM1H 02 ...
Page 124: ... MEMO WUME GM1H 02 ...
Page 125: ... MEMO WUME GM1H 02 ...
Page 126: ...Panasonic Corporation 2021 August 2021 WUME GM1H 02 ...