background image

4466

Fire alarm solutions

technical description

EXTERNAL 

POWER SUPPLY

www.panasonic-fire-security.com     

Summary of Contents for 4466

Page 1: ...4466 Fire alarm solutions technical description EXTERNAL POWER SUPPLY www panasonic fire security com...

Page 2: ...SECURITY FUNCTIONS 11 4 5 VOLTAGE OUTPUTS OUT0 AND OUT1 12 4 6 OUTPUT SIGNAL OK 12 4 7 SHORT CIRCUIT ISOLATOR 13 4 8 FUNCTIONAL OVERVIEW 14 4 9 FAULTS 14 5 CURRENT CONSUMPTION CALCULATION 15 6 CONFIGU...

Page 3: ...4466 EXTERNAL POWER SUPPLY FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 3 11 COMMISSIONING 26 11 1 USING AUTOMATIC ADDRESSING 26 11 2 USING MANUAL ADDRESSING 26 12 TECHNICAL DATA 27 13 APPROVALS 28...

Page 4: ...FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 4 1 INTRODUCTION This document describes the external power supply type number 4466 The document contains information about the product and instructions on h...

Page 5: ...RNAL POWER SUPPLY FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 5 2 ABBREVIATIONS CIE Control and indicating equipment control unit EOL End of line PC Personal Computer SMPS Switch Mode Power Supply S W...

Page 6: ...xplosion if batteries are replaced by incorrect type See 4 4 BACKUP BATTERY on page 8 4 Caution Risk of electric shock Make sure to disconnect the fuse F2 for the backup batteries before touching any...

Page 7: ...6 has a build in short circuit isolator It is possible to mount and connect two the 2 voltage outputs board and or the com loop repeater 4585 inside the 4466 i e in total two expansion boards The exte...

Page 8: ...ng current mode 4 3 1 FUSES There are four fuses on the charger board F1 T5AH 250 V 5x20mm 24V DC rectifier input F2 T5AH 250 V 5x20mm battery input F3 T2AH 250 V 5x20mm 24V DC output 0 or connector J...

Page 9: ...otal battery capacity Q QN QA Ah The battery voltage at the end of a discharging period is not the same as at the start Round up the calculated capacity and add at least 20 margin at room temperature...

Page 10: ...ommended to use the low current charging mode See the following table Charging mode Jumper JP1 Battery capacity Ah Imax a IOut0 IOut1 24 V DC output Continuous current takeout A Low current Open 12 3...

Page 11: ...e to be charged again A new charging cycle will then start The duration of step 1 and step 2 respectively is depending on the battery condition when the charging started 4 4 5 SECURITY FUNCTIONS The u...

Page 12: ...ax b IOut0 IOut1 No charging Imin Low current 7 2 Ah 0 3 0 4 0 0 Low current 7 2 Ah 1 2 0 2 0 0 Low current 7 2 Ah 2 0 0 0 High current 42 Ah 0 1 5 4 0 0 High current 42 Ah 1 0 5 2 0 0 High current 42...

Page 13: ...ax 30V DC The nominal line voltage Vnom 24V DC The minimum line voltage Vmin 12V DC The maximum rated continuous current with the switch closed IC max 350 mA The maximum rated switching current on sho...

Page 14: ...to be used if an expansion board is supplied from the output 2 Alarm devices 3 EOL Device 4 Fire door release magnet 5 Addressable units 6 COM sub loop 4 9 FAULTS The 4466 is generating fault signal...

Page 15: ...Calculate the total continuous current consumption from both outputs boards excluding the battery charging in alarm state ITA When the backup battery is the power source the current consumption for th...

Page 16: ...ions for the system a In EBLWin right click on a loop Add loop unit 4466 External power supply b In the 4466 External power supply properties window set the following Technical address automatically s...

Page 17: ...al address plus one The unit connected to power supply output J6 must have the 4466 technical address plus two For more information on units 4464 and 4585 see the technical description for each unit 7...

Page 18: ...and 4585 also must be changed if mounted a Disconnect the 4466 from the COM loop b Reset the address for PCB 4464 4585 according to the instruction RESET ADDRESS in technical description for 4464 or...

Page 19: ...setting tool 4414 according to the table below 8 1 COMPATIBILITY TABLE Advanced mode NORMAL mode 2330 mode 2312 mode EBL512 G3 V 2 5 All versions Not used Not used EBL128 V 2 5 All versions Not used N...

Page 20: ...ied b Make sure the housing is mounted with the cable gland plate upwards The 4466 weighs 10 kg including batteries Use screws of sufficient dimension Make sure the wall is suitable for this purpose P...

Page 21: ...all place the batteries and fasten the battery bracket d Make holes for the cables in the cable gland plate with a sharp tool e Connect the 4466 according to 10 INSTALLATION AND WIRING on page 23 f At...

Page 22: ...ds according to the picture below Screws are supplied with the expansion boards separately b Connect each Molex connector to contact header J2 on the expansion board and to contact header J5 or J6 on...

Page 23: ...before making any service except address setting in the 4466 10 1 POWER SUPPLY WIRING When connecting the mains to the SMPS connect to a household removable fuse intended for this unit only and marked...

Page 24: ...65 mm 0 33 mm 1 6 mm 2 mm Terminal block J3 2 3 mm 4 mm Terminal blades J1 batteries Depending on the spade terminal type Wire size Min Wire size Max 1 4 mm 1 5 mm 2 8 mm 6 mm 10 2 2 ELECTRICAL INTERF...

Page 25: ...be connected to number 1 and number 2 in terminal block J2 in 4466 10 4 CHECK LIST The following has to be connected Mains is to be connected to the Terminal Block L line N neutral safety earth Batte...

Page 26: ...J1 h When 4466 and all other units are properly installed on the loop connect the system to the mains i Put back the fuses in this order F3 F4 F1 F2 j Attach the lid See section 9 MOUNTING f on page 2...

Page 27: ...rm is activated in the system 24 V DC 16 29 5 V DC 2 0 A 3 0 A alternative 1 5 A low or high charging mode 4 A Batteries Inside the housing two batteries Outside the housing 7 2 Ah L x W x H 151 x 64...

Page 28: ...otified body CPR EN54 4 EN54 17 EN54 18 VdS No 0786 CPR 21627 VdS EN54 4 EN54 17 EN54 18 VdS 2344 VdS 2541 VdS No G219025 EMC EN 55032 Class A1 Emission EN 50130 4 Immunity Self declaration VdS LVD EN...

Page 29: ...ESCRIPTION 4466 DOCUMENT NUMBER MEW01878 EN DATE OF ISSUE 2019 04 05 REV 3 DATE OF REVISION 2022 06 13 Panasonic Fire Security Europe AB Jungmansgatan 12 SE 211 11 Malm SE Tel 46 0 40 697 70 00 www pa...

Reviews: