                                                                                                                                                                                                                                                  fire products and solutions

   

 

 

Fire System Technology

 

 

Fire Panels - Accessories 

 
  Fire Alarm Systems Address Setting Tool

 

 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

Model  4414 

 

Used for COM loop address and mode settings 

 

 

COM loop address setting  

 

Address setting tool 4414 is used to set the COM loop 
unit's 

address 

(001-255) on the analogue detector types 

33xx / 430x / 440x and all other addressable COM loop 
units (33xx / 43xx / 44xx). 
 

Mode setting 

 

The address setting tool 4414 is also used to set the 
COM loop unit's 

mode

M0 

= NORMAL mode  

M1 

= 2330 mode (COM loop address 001-127)  

M2 

= 2312 mode (COM loop address 001-127)  

M3 

= Advanced mode See instructions for the COM loop 

unit respectively.

 

 

Connection cable 

 

Some units have flying leads and some units only screw 
terminals. A connection cable with insulated crocodile 
clips and push-on terminals is supplied with the address 
setting tool, to be used for the COM loop units that 
cannot be plugged directly on the tool.

 

 

Product applications 

 

Used for address and mode settings when analogue 
detectors and other addressable COM loop units are to 
be used in the systems FT128V2 and FT1020G3.  
4414 has to be used to set the analogue detectors 440x 
in Advanced mode.

 

 
 

 

 
 

 

User friendly 

 

The address setting tool is powered by four 1.5 V Alkaline 
batteries (LR6 / AA). Battery life time is approx. 250 hours or 
up to 50000 readings / writings.  
An analogue detector's contact pins (SA / SB) are plugged into 
the address setting tool's snap connectors (SA / SB). The 
connection cable is used to connect to other units.  
The tool is turned on by the 

On/Off / CLR 

button. "MØ" and a 

blinking cursor will be shown in the display. 

 

How to read: 

 

Turn on the tool.  

Press the 

Read 

button.  

Wait for a beep ("READ" will be shown in the display).  

 "OK", the address and the mode will be shown in the display.  
 

How to write: 

 

Turn on the tool.  

Default mode is M0 (NORMAL mode). The mode can be 
changed by pressing the 

Write 

and 

Read 

buttons at the same 

time and then select a mode (0-3).  

Type the COM loop address (001-255)  

Press the 

Write 

button.  

Wait for a beep ("WRITE" will be shown in the display).  

"OK", the address and the mode will be shown in the display.  
 
Write the COM loop address on the Address label on the COM 
loop unit respectively.  
If the tool is not used for approx. 20 seconds, it will be 
automatically turned off in order to save the batteries

.

 

 

 

 

 