TMO2D User’s Manual
7
Chapter 2. Installation
2.3.2 XMO2 Transmitter
Wiring the XMO2 oxygen transmitter to the TMO2D display requires use of the X4(*) cable, which can support
distances up to 450 ft (130 m). For longer distances, each cable can be supplied as 18-AWG that can be located up to
1,050 ft. (320 m). If you are using your own cable, refer to Table 3 below for cable requirements.
For longer cable lengths, consult the factory.
2.3.2.1
Wiring:
Use the following steps to interconnect the XMO2 to the TMO2D.
1.
Route the 4-wire power/analog output cable through a cable gland as shown in Figure 3 below.
2.
After terminating the shield as shown, assemble the three gland pieces together and tighten the gland to secure
the cable and the shield.
IMPORTANT:
The cable shield must be terminated in the cable gland as shown in Figure 3 below.
Figure 3: Proper Cable Gland Assembly
3.
Route the cable into the XMO2 transmitter through one of the 3/4" conduit holes on the side of the transmitter.
WARNING!
Be sure to plug the unused conduit/cable entry hole on the transmitter, in order to meet
specifications and to maintain the appropriate weatherproof or explosion-proof rating.
4.
Unplug terminal block TB1/TB2 on the XMO2 transmitter PC board (PCB) by carefully pulling it directly up without
bending the pins attached to the PCB. (See Figure 4 on page 8.)
5.
Loosen the TB1 side screws and insert the colored wires into the corresponding openings on top of TB1. See Table 4
on page 7 for color-coded pin designations.
Table 3: Cable Requirements for XMO2
MAX. CABLE LENGTH
CABLE SIZE
MAX. CABLE LENGTH
CABLE SIZE
Feet
Meters
AWG
Sq. mm
Feet
Meters
AWG
Sq. mm
450
130
22
0.35
1,700
500
16
1.2
700
200
20
0.6
2,800
850
14
2.0
1,050
320
18
1.0
4,000
1,200
12
3.0
Table 4: Wiring the XMO2 with 4-Wire Cable
Wire Connections
Color
XMO2 Transmitter TB1
TMO2D Display TB5
Power +24 VDC
Red
Pin 1
+24 V
Power Return
Black
Pin 2
RTN
+ mA Signal
White
Pin 3
GAS
–mA Signal
Blue or Green
Pin 4
RTN
Cable Shield
Summary of Contents for TMO2D
Page 1: ...panametrics com Process Analyzers 910 084 D August 2021 TMO2D Digital Display User s Manual...
Page 2: ......
Page 4: ...ii no content intended for this page...
Page 10: ...Chapter 1 Features and Capabilities 2 TMO2D User s Manual no content intended for this page...
Page 24: ...Chapter 2 Installation 16 TMO2D User s Manual no content intended for this page...
Page 26: ...Chapter 2 Installation TMO2D User s Manual 18...
Page 64: ...Chapter 4 Basic Programming 56 TMO2D User s Manual no content intended for this page...
Page 74: ...Chapter 6 Specifications 66 TMO2D User s Manual no content intended for this page...
Page 87: ...Appendix A Outline and Installation Drawings TMO2D User s Manual 79...
Page 89: ...Appendix B Menu Maps 81 TMO2D User s Manual no content intended for this page...
Page 94: ...Appendix B Menu Maps TMO2D Digital Display User s Manual 86 Figure 30 Factory Setup Menu...
Page 95: ...Appendix B Menu Maps TMO2D Digital Display User s Manual 87...
Page 99: ...76 TMO2D User s Manual no content intended for this page...
Page 100: ......