Setting up the RTD Inputs
Option cards with RTD inputs have a temperature range of –100° to 350°C. Complete the following steps to set up the
two RTD inputs of an option card installed in Slot x:
1.
Press
[F1]
to set up RTD input A or
[F2]
to set up RTD input B.
Note:
The setup of RTD input A is used as an example. Identical procedures would be used to set up RTD input B.
2.
Enter a label of up to eight characters and press
[ENT]
.
3.
At the
Input Measurement prompt, press
[F1] = OFF
to disable RTD input A and return to the previous prompt, or
press
[F2] = TEMP
to enable RTD input A.
4.
Enter the
Zero Value for the low end of the chosen input range and press
[ENT]
.
5.
Enter the
Full Scale Value for the high end of the chosen input range and press
[ENT]
.
6.
Press
[F1]
-
[F2]
to set up another input or press
[EXIT]
to select another slot for set up.
For instructions on setting up additional inputs and/or outputs, proceed to the appropriate section. Otherwise, press
[EXIT]
twice to return to the
Global PROGRAM
prompt.
Procedure Options
After completing the above steps, the meter returns to the
Global I/O
prompt. Continue as follows:
• To continue programming the meter, refer to the menu maps in Appendix A and navigate to the desired menu.
Then, proceed to the appropriate section of this manual for instructions.
• To leave the
User Program and retain the previous settings, press
[EXIT]
twice and then press
[F1] = NO
at the
SAVE prompt. Any programming changes will be discarded and you will be returned to the data display.
• To leave the
User Program and return to measurement mode, press
[EXIT]
twice and then press
[F2] = YES
at
the
SAVE prompt. Your programming changes will be entered into the meter’s memory, and you will be
returned to the data display.
Summary of Contents for DigitalFlow GS868
Page 2: ......
Page 4: ...ii no content intended for this page...
Page 10: ...Contents viii DigitalFlow GS868 Programming Manual 2 Channel...
Page 91: ...DigitalFlow GS868 Programming Manual 2 Channel 81 Appendix A Menu Maps...
Page 92: ...82 DigitalFlow GS868 Programming Manual 2 Channel...
Page 100: ...DigitalFlow GS868 Programming Manual 2 Channel 90...
Page 104: ...94 DigitalFlow GS868 Programming Manual 2 Channel no content intended for this page...
Page 122: ...112 DigitalFlow GS868 Programming Manual 2 Channel no content intended for this page...
Page 136: ...126 DigitalFlow GS868 Programming Manual 2 Channel no content intended for this page...
Page 140: ...Index 4 DigitalFlow GS868 Programming Manual 2 Channel...
Page 144: ...Chapter 2 DigitalFlow GS868 Programming Manual 2 Channel...
Page 145: ......