Install the PA-5200 Series Firewall in an Equipment Rack
Install the Four-Post Rack Kit on a PA-5200 Series
Firewall
The following procedure describes how to install the oponal four-post rack kit (PAN-PA-5200-
RACK4) to provide addional support to the back of the firewall. This kit supports rack depths
from 23 to 32 inches (measured between the inner-parts of the vercal rails).
STEP 1 |
Aach one rack-mount bracket to each side of the firewall in the front-mount posion using
nine #8-32 x 5/16” screws for each bracket and torque to 15 in-lbs.
STEP 2 |
Aach one rack-mount rail to each side of the firewall using four #8-32 x 5/16” screws for
each bracket and torque to 15 in-lbs. The side brackets are universal but you must install
them with the beveled edge facing the firewall.
STEP 3 |
With help from two other people, hold the firewall in the rack and secure the rack-mount
brackets to the front rack posts using four screws for each bracket. Use the appropriate