Positioning of the remote cooling unit
Placing the cooling unit
The cooling unit may be placed both inside and outside. In any case, sufficient air circulation must be
provided (see also schematic diagram).
If it is placed outside, a sufficiently large lockable protective shelter must be provided.
If the cooling unit is placed inside in front of a opening in the wall, the following measures have to be
taken:
-
Keep a free area of at least 25 cm between the wall and the condenser.
-
Make an opening in the wall that the condenser is standing against which is at least as large as the
condenser is.
-
In the wall opposite the condenser, make an opening the size of the condenser for the evacuation of hot
air.
If the cooling unit is placed inside in front of a closed wall, the following measures have to be taken:
-
Keep a free area between the wall and the consensor equal to the following formula:
L
H
H
L
2
L = length, H = height of the condensing unit
-
Make sure there is enough ventilation
In cold weather, the front of the condenser may be partly covered.
If the condenser is in a place where the temperature is always lower than 5°C, a high-pressure switch
should be placed to control the fan motor(s).
It must
not
be possible for the cooling unit to suck in the exhaust gases of the vacuum pump of the milk
machine.