SECTION 4:  OPERATIONS 

Start Up 

The BGS32 ships fully preconfigured. Once power is supplied, the system will automatically 
connect to any Gateway that is within range and set to the same radio zone.  
 

 
Each BGS32 contains up to four component meters. Each meter has LEDs that glow when 
powered on. The cover of the BGS32 allows viewing the LEDs making it possible to verify 
that all component meters are powered up and that the lights on the units are flashing in a 
consistent manner. 
 
Each BGS32 has a unique 16-digit ID number that can be found on a label located on the 
outside of the unit in the top left corner. Each component meter also has a unique 16-digit ID 
number on the meter’s front label. Once the meter makes a wireless connection to a Gateway, 
the readings from that meter can be accessed via the Gateway’s console.  
 

 
Packet Power provides documentation that is unique to each BGS32 and associates each CT 
to its component meter. See Appendix for sample. This documentation is required in order to 
access readings using protocols such as SNMP or Modbus. Customers using Packet Power’s 
EMX application will be provided with panel maps to load into EMX.  
 
At initial start-up, it is highly recommended to validate correct operations by placing a 
known load on each circuit and verifying that the load is correctly reflected by the system, 
first at the Gateway console to validate the physical connection, and then in the monitoring 
application to validate the mapping logic.  

Operation 

Normal operation is characterized by the regular flow of monitoring data. This is typically 
verified on a continual basis via the site’s monitoring application. Please consult the 
monitoring application’s documentation for how to achieve this using your application. 
 

To prevent damage to the BGS32, ensure power is 
disconnected whenever abnormal or extreme 
power conditions may exist such as during 
infrastructure commissioning. 
 

Instructions for accessing the Gateway console can be 

found on the Packet Power web site:

 

https://dox.packetpower.com/Ethernet---Gateway---

Version---4---Web---Console.html

 

Summary of Contents for BGS32

Page 1: ...Multi Circuit Monitor BGS32 User Manual Version 2 0 BGS32 Multi Circuit Monitoring System Installation Operations and Maintenance Manual Version 2 0 Packet Power 2716 Summer St NE Minneapolis MN 55413...

Page 2: ...ice Current transformers shall provide two means of isolation from hazardous voltages When selecting a current transformer the voltage and measurement category of the circuit to be measured must be co...

Page 3: ...ailure to observe the information following this symbol may result in injury or death CAUTION This system and the area it is installed in may contain life threatening voltages Qualified personnel must...

Page 4: ...ssembly This product has been tested to the following requirements UL508A Industrial Control Panel Class B Device Statement Section 15 105 a of the FCC Rules This equipment has been tested and found t...

Page 5: ...a supplement to information provided in the support section of Packet Power s web site www packetpower com support The BGS32 must be used in conjunction with a Packet Power Ethernet Gateway Detailed...

Page 6: ...rrent Transformers 7 Communication 8 Components 9 SECTION 3 INSTALLATION 10 Installation Overview 10 Mounting 11 Voltage Connection 13 CT Interconnect Cables and Boards 16 CT Leads 16 CTs 17 SECTION 4...

Page 7: ...ou are monitoring matches the type indicated on the label of the BGS32 The BGS32 cannot be used on 480V equipment if access to N is not present nor on 600 347V circuits The BGS32 is powered from the v...

Page 8: ...ateways can be added for capacity or redundancy The BGS32 must be able to establish a wireless connection either directly to a Gateway or to another Packet Power wireless device Data can be accessed f...

Page 9: ...tor BGS32 User Manual V2 0 2021 Packet Power LLC Page 9 of 29 Components The BGS32 consists of a NEMA 1 monitoring enclosure two CT interconnect boards with loose CT leads or wire harnesses for attach...

Page 10: ...list of safety instructions in the Hazards sections of this document Installation Overview The BGS32 does not need to be configured prior to use 1 Mount the BGS32 to wall or device using mounting tab...

Page 11: ...2021 Packet Power LLC Page 11 of 29 Mounting The BGS32 should be mounted as close as possible to the equipment being monitored Mounting locations Use the mounting tabs provided for wall mount or the...

Page 12: ...r wire exits in the back bottom and on each side of the enclosure allowing it to be mounted in a variety of positions relative to the equipment being monitored Wire exit location Description Bottom 1...

Page 13: ...ge disconnect near the BGS32 that is used to avoid placing strain on the connection to the terminal block during shipping and installation 5x20 mm 5A inline fuses are included on L1 L2 and L3 unless o...

Page 14: ...Packet Power Multi Circuit Monitor BGS32 User Manual V2 0 2021 Packet Power LLC Page 14 of 29 Voltage wire connections by service type...

Page 15: ...Packet Power Multi Circuit Monitor BGS32 User Manual V2 0 2021 Packet Power LLC Page 15 of 29...

Page 16: ...sure to orient the CT Interconnect Board so the black connector header faces away from the circuits or panel Attach Interconnect Cables to Interconnect Boards Attach the connector at the end of the C...

Page 17: ...ch CT lead will have a label standard labels are CT1 CT2 CT3 etc CTs The BGS32 supports 9 to 32 split core or Rogowski coil CTs of varied amperage and size SPLIT CORE CTs Split core CT Specifications...

Page 18: ...d into place Connect CT tails to CT leads CT leads coming from the CT Interconnect Board will typically be labeled CT1 CT2 CT3 etc unless otherwise specified Connect the CT tail to the corresponding C...

Page 19: ...ion the coil on the conductor such that the arrow on the connector faces toward the load and away from the source 4 Close the Rogowski coil and ensure the closing unit has clicked into place Connect R...

Page 20: ...and associates each CT to its component meter See Appendix for sample This documentation is required in order to access readings using protocols such as SNMP or Modbus Customers using Packet Power s...

Page 21: ...es Follow the wire harness on the side of the terminal block that feeds into the BGS32 to locate the inline fuse holders Open each fuse holder and inspect for blown fuses Replace with 5x20mm glass 5A...

Page 22: ...en entered on the master gateway If V readings are present but A and W are missing o If only one reading is missing follow the process listed in the Maintenance section of this document to remove the...

Page 23: ...ENANCE Equipment Parts List Contact Packet Power support if you encounter issues related to any parts or before attempting any repairs Of these items the following can be replaced in the field by qual...

Page 24: ...LIT CORE CT 1 Disconnect power to the BGS32 if possible If it is not possible to disconnect power always treat CT leads as though they carry line voltages Work on live panels must only be performed by...

Page 25: ...uick disconnect attached to the cable 3 Open the Rogowski coil by pinching the closing unit on the side of the connector and remove from the conductor 4 Position the new coil on the conductor such tha...

Page 26: ...LLC Page 26 of 29 Dismantling The BGS32 contains components that may fall under local electronics disposal guidelines Please adhere to local requirements No lead is used in the BGS32 Emergency Measure...

Page 27: ...based on customer provided information e g panel name etc E The radio zone that the meters in the BGS32 are set to F The location at which the wires will exit the BGS32 enclosure G The type of voltag...

Page 28: ...Packet Power Multi Circuit Monitor BGS32 User Manual V2 0 2021 Packet Power LLC Page 28 of 29 C D E A B F G H I...

Page 29: ...Packet Power Multi Circuit Monitor BGS32 User Manual V2 0 2021 Packet Power LLC Page 29 of 29...

Reviews: