AFX SERIES® OPERATION MANUAL
Rear Panel, Connectors and Protection
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 197 of 485
7.3.7.2
SYNC Status Display
A “Synced” status field will be displayed in
Green
in the lower left corner of the LCD display.
This field will toggle with the regular “Ready/Enabled/Fault” status field also shown in this
location. The “Synced” status will be shown every 3 seconds for 1 second in place of the
“
Ready/Enabled/Fault” field. When the PLL is not locked to the external source, the unit will
display an “Unsynced” status in
Orange
.
It is not recommended to enable the unit when it has not locked or synchronized to the
external source because the frequency may be unknown.
Figure 7-5: External Sync Input Sync Status Indication
Figure 7-6: External Sync Input Sync Lost Status Indication
7.3.7.3
Sync Operation Settings
The AFX allows precise configuration of the synchronization parameters to optimize
performance for each application. The parameters are:
1
Phase shift
: Defines a fixed phase shift between phase A waveform generation and
the external sync source. Used to calibrate any phase difference between the sync
signal and the power source output on phase A.
Command: SOURce:SYNChronize:PHASEshift
2
Speed
: Allows accelerating the speed of the internal synchronization engine (PLL) in
case the external sync source is not constant and presents periodic or continuous
Summary of Contents for AFX Series